7. PLC2Way
3-51
Ser
• $s762
Periodical reading that is set in the [Temp. CTRL/PLC2Way Table Setting] dialog can be 
suspended.
- [0]:
Periodical reading is performed.
- [Other than “0”]: Periodical reading is suspended.
If periodical reading of the temperature control network/PLC2Way table is performed 
while the PLC2 memory is being accessed using a macro command, the macro 
execution will be delayed (Fig. a).  To avoid this, periodical reading can be suspended 
using memory address $s762 (Fig. b).
• $s763
Forced execution of macro commands [TEMP_READ] and [TEMP_WRITE] using the 
temperature control network/PLC2Way table
- [0]:
When any station that has failed is included in the specified table, 
the macro command is not executed.
- [Other than “0”]: The macro command is forcibly executed to the stations that are 
working properly.
TEMP_CTL $u100 2
TEMP_CTL $u110 2
TEMP_CTL $u120 2
TEMP_CTL $u300 2
T
t
TEMP_CTL $u100 2
TEMP_CTL $u110 2
TEMP_CTL $u120 2
TEMP_CTL $u300 2
T+t
T
T
$s762=1
TEMP_CTL $u100 2
TEMP_CTL $u110 2
TEMP_CTL $u120 2
TEMP_CTL $u300 2
$s762=0
$s762=1
TEMP_CTL $u100 2
TEMP_CTL $u110 2
TEMP_CTL $u120 2
TEMP_CTL $u300 2
$s762=0
t
(Fig. a)
Execution of macro “a”
Execution of macro “a”
Temperature control 
network/PLC2Way table 
periodical reading
V7 communication cycle
Execution of macro “b”
Execution of macro “b”
Temperature control 
network/PLC2Way table 
periodical reading
Temperature control 
network/PLC2Way 
table periodical reading
Temperature control 
network/PLC2Way 
table periodical reading
V7 communication cycle
• TEMP_READ
• TEMP_WRITE
• TEMP_CTL
• MOV, BMOV, BSET,
BCLR, BINV
When the PLC2 memory is 
used for the above command:
(Fig. b)