Epson V7 User Manual

Page of 344
5-122 
24. YAMATAKE PLC
24. YAMATAKE PLC
Available PLCs
Communication Setting
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Available Memory
The available memory setting range varies depending on the PLC model.  Be sure to set within the 
range available with the PLC to be used.  Use [TYPE] when assigning the indirect memory for macro 
programs.
Select PLC Type
PLC
Unit/Port
Connection
MX series
MX200/MX50
ASCII connector
RS-232C
[Wiring Diagram 1]
Item
Setting on PLC
V7 Comm. Parameter Setting
Baud rate
9600 bps
9600 bps
Port
1
1
Parity
Even
Even
Transmission code
Data length
8
8
Stop bit
1
1
Memory
TYPE
Remarks
R
(data register)
0
M
(auxiliary relay)
1
L
(latch relay)
2
X
(input relay)
3
Y
(output relay)
4
TP
(timer/current value)
5
TS
(timer/setting value)
6
CP
(counter/current value)
7
CS
(counter/set value)
8
T
(timer/contact)
9
C
(counter/contact)
10
P
(link register)
11