25. TAIAN PLC
25. TAIAN PLC
Available PLCs
Communication Setting
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Available Memory
The available memory setting range varies depending on the PLC model.  Be sure to set within the 
range available with the PLC to be used.  Use [TYPE] when assigning the indirect memory for macro 
programs.
Select PLC Type
PLC
Unit/Port
Connection
TP02
TP02
Communication Port 
(T/R+, T/R
−)
RS-422
[Wiring Diagram 1]
MMI Port (9pin)  
(4-5 Short Computer 
Link Mode)
RS-422
[Wiring Diagram 2]
Item
Setting on PLC
V7 Comm. Parameter Setting
Baud rate
19200 bps
19200 bps
Port
1
1
Parity
Not provided
Not provided
Transmission code
Data length
7
7
Stop bit
1
1
Memory
TYPE
Remarks
D
(data register timer•counter/contact)
0
V
(timer•counter/contact)
1
WS
(system register)
2
WC
(constant register)
3
X
(input relay)
4
Y
(output relay)
5
C
(internal relay)
6
SC
(special register)
7