Liebert MultiLink Response to UPS Events—Typical Sequence
82
Liebert
®
 MutiLink
®
UPS Operating On Battery
When Liebert MultiLink detects a UPS Operating On Battery event, the following occurs:
1. A UPS Alert is displayed.
2. If the Command action (available in Liebert MultiLink Advanced only) is enabled:
• A timer starts that may lead to executing a command that the user or System Administrator 
has written to perform site-specific operations for applications that have command-line 
options.
• If this timer expires—the duration specified during configuration—the script is executed.
• To cancel the Command action manually, open the MultiLink Viewer, select the Event 
Configuration tab and remove the check mark (✔) from the Enable Command Action box. 
Click on MultiLink, then on Save.
3. If the Shutdown action is enabled:
• A shutdown timer begins when UPS Operating On Battery occurs. The timer’s duration is 
specified during configuration.
• If this timer expires before the canceling event UPS Output Returned From Battery 
occurs, the operating system is shut down.
• Liebert MultiLink notifies the user that a shutdown is impending.
• When two minutes remain on the shutdown timer, the MultiLink Countdown to 
Shutdown box opens.
• Clicking on Cancel Shutdown overrides the configuration 
settings and prevents the operating system from being shut 
down. A dialog box asks for confirmation before the shutdown 
is canceled.
• Clicking on the Pause Shutdown button suspends the 
shutdown process, including the timer. A dialog box confirms 
that the shutdown is paused and offers the options of canceling 
the shutdown or resuming the countdown toward an orderly 
shutdown of the operating system.
Timer . . .
. . . shows seconds 
remaining until 
operating system 
is shut down.
Cancel Shutdown
Pause Shutdown