Emerson Liebert MC Microchannel Outdoor Condenser 28 - 220kW User Manual

Page of 68
Site Preparation
9
Liebert
®
 MC
Figure 5
Condenser planning dimensions–MCM120
Leg Height
A *, In. (mm)
B
In. (mm)
C
In. (mm)
18 (457)
31-5/8 (803)
39-5/8 (1006
36 (914)
49-5/8 (1260)
57-5/8 (1464)
48 (1219)
61-5/8 (1565)
69-5/8 (1768)
60 (1524)
73-5/8 (1870)
81-5/8 (2073)
* 18" legs standard for all models. Cross-bracing required for legs longer than 18". Number varies according to model and options.
See Tables 1 and 2 for weights, including added weight for legs of various lengths.
Source: DPN002555, Rev. 1
A
Shown with typical 60" legs.
152-3/4"
(3880mm)
46-1/4"
1175mm
B
C
A
144-5/16"
(3666mm)
Liebert DSE receiver adds
8-1/2" (216mm) to the unit
width and may be mounted
on the right or left side.
DETAIL A
Electrical Box End
46"
(1169mm)
Fastener assembly,
fender washer and
hex nuts.
4 each required,
2 places
Spacer
2 each required,
2 places
Emerson recommends a clearance of
36" (915mm) on each end and each side
for proper operation and component access.
46-5/16" (1177mm)
39-5/16"
(999mm)
44-3/8"
(1127mm)
1-7/8"
(48mm)
94-7/16"
(2398mm)
Install two (2) each 1/8"(3.18mm)
leg spacers in each of these
locations (see note below)
NOTE:
Install (2) two condenser leg spacers, part number 304679P1, in two places where shown, between each pair of legs
that adjoin each other.
Use (4) four of part number: 301375G1 (fastener assembly), 301369P1 (washer fender) and 301392P1 (nut hex),
to secure each pair of legs and spacers together.
DPN002555
Rev. 1
ANCHOR PLAN
For typical footprint 
dimensions, see Figure 2
See table below for 
dimensions A, B and C