Emerson Liebert MC Microchannel Outdoor Condenser 28 - 220kW User Manual
Inspection and Installation
15
Liebert
®
MC
™
3.5
Preparing a Condenser for Moving and Installation—Units with One or Two Fans
The following procedure is one recommended method for removing a Liebert condenser from its
shipping skid. Other methods may be used, provided that they are safe for personnel, the condenser
and equipment.
3.5.1 Attaching Legs, Removing the Skid and Attaching Slings-Units with One
or
Two Fans
1. Attach legs to the unit at indicated locations.
Use the fasteners provided with the legs.
Recommended tools for attachment is a 5/8" socket and ratchet.
More legs may be available for installation than shown. This will depend on the unit type and
Recommended tools for attachment is a 5/8" socket and ratchet.
More legs may be available for installation than shown. This will depend on the unit type and
number of fans.
Figure 11 Attaching legs to one-fan or two fan condensers
2. Place slings around the unit between the unit and the top deck boards of the skid:
• One-fan and two-fan units: against the inside of the attached legs.
• Three-fan and four-fan units: against the outside of the attached eye bolts.
• Three-fan and four-fan units: against the outside of the attached eye bolts.
3. Use spreader bars, a lift beam and a crane to lift the unit off the skid.
NOTICE
Risk of improper lifting. Can cause equipment damage.
Make sure that the spreader bars wider are than the unit. If the spreader bars are too short,
Make sure that the spreader bars wider are than the unit. If the spreader bars are too short,
the slings may crush the unit.
Figure 12 Securing slings to condensers for lifting off skid
Detail B
B
308111
Rev. 1
308111
Pg. 2, Rev. 1
Straps go against
legs on one-fan and
two-fan units
Straps or chains go against
eyebolts on three-fan and
four-fan units