Emerson Liebert MC Microchannel Outdoor Condenser 28 - 220kW User Manual

Page of 68
Inspection and Installation
17
Liebert
®
 MC
Figure 14 Lifting condensers with one, two, three or four fans
3.6
Mounting the Condenser
The condenser must be installed so that it is level within 1/2" (13mm) to ensure proper refrigerant 
flow. For roof installation, mount the condenser on suitable curbs or other supports; follow all local 
and national codes. Secure the legs to the mounting surface using a field-supplied 1/2" (13mm) 
diameter bolt in each of the two 1/2" x 1" (12.7x25.4mm) obround holes in each leg. See Figures 3 
through 7 for anchor dimensions.
Spreader Bars 
(must be wider 
than the 
Liebert MC to 
prevent crushing 
force)
Straps go through holes in legs 
on one-fan and two-fan units
Straps or chains go through 
eyebolts on three-fan and 
four-fan units
308111
Pg. 3, Rev. 1