Emerson Liebert MC Microchannel Outdoor Condenser 28 - 220kW User Manual

Page of 68
Piping
27
Liebert
®
 MC
Figure 18 Piping schematic
Service/Schrader (Access) Connection With Valve Core
NOTES
Single refrigeration circuit shown for clarity.
Schematic representation shown. Do not use for specific connection locations.
* Components are not supplied by
   Liebert but are recommended for
   proper circuit operation and
   maintenance
Refrigerant Piping
Field Piping
Service/Schrader (Access) Connection No Valve Core
Trap at base of risers
over 5ft. (1.5m)*
Condenser
Coil
Condenser
Coil
Liebert Lee-Temp Receiver
Liebert Lee-Temp
Hot Gas Discharge
Liquid Return
For rises over 25ft. (7.6m),
trap every 20ft. (6m) or at
evenly divided distances*
Evaporator
Coil
Liquid
Suction
Compressor
Expansion
Valve 
Solenoid
Valve
Sight
Glass
Filter Drier
Liquid Line
Hot Gas Discharge
*Isolation
Valve
*Isolation
Valve
Check
Valve
Field installed relief valve(s) required
for 50Hz EU CE units
Optional Field-Installed
Fusible Plug
Service
Valve
Check Valve
Relief Valve
Service
Valve
Head Pressure
Control Valve
Service
Valve 
External
Equalizer
Sensing
Bulb
DPN002188
Rev. 1