Piping
29
Liebert
®
 MC
Figure 19 Liebert MC Condenser piping—Single-circuit units
Table 6
Liebert MC Condenser piping sizes, single-circuit units
Model No.
Number
of Fans
Connection Sizes, OD, in (mm)
Hot Gas Line
Liquid Line
MCS028
1
7/8
5/8
MCM040
1
7/8
5/8
MCM080
2
1-1/8
7/8
MCM120
3
1-3/8
7/8
MCL055
1
1-1/8
7/8
MCL 110
2
1-3/8
1-1/8
MCL 165
3
1-3/8
1-1/8
MCL 220
4
1-5/8
1-3/8
A
Leaving
Liquid
Line
Entering
Hot Gas
Line
Horizontal
Vertical
Optional fusible plug service kit to be brazed into the liquid line(s)
in either the vertical or horizontal position (where required).
Vertical position is preferred; horizontal position is optional.
DPN002166
Rev. 1
Field Piping
Fan 1
Fan 2
Note: Inverted traps in 
refrigerant lines are internal 
to the Liebert MC condenser 
and field-installation is not 
needed.