Troubleshooting
Liebert
®
MC
™
60
10.0 T
ROUBLESHOOTING
Table 19
Troubleshooting
Symptom
Possible Cause
Check or Remedy
Condenser will not start
No power to condenser.
Check voltage at input terminal block.
Circuit breaker or fuse for low-voltage
transformer in condenser is tripped.
Locate problem in condenser electrical panel and
repair.
No low-voltage signal to/from indoor
unit.
Locate open circuit and repair.
Low discharge pressure
Faulty head pressure control valve or
condenser control board (PEC/BEC).
Replace if defective.
High discharge pressure
Dirty condenser fins.
Clean coil.
Condenser fans not operating.
Check for low-voltage signal from indoor unit.
Check fan motors and fuses.
Check fan motors and fuses.
High refrigerant charge
Check refrigerant charge.
SPD green and red LEDs
are extinguished
No voltage or improper phasing exists
at condenser.
Check voltage at input terminal block.
Electrical connections to SPD are faulty.
Locate connection problem and repair.
Condenser disconnect is turned Off.
Recheck lights with disconnect switch in the On
position.
SPD red LED is
illuminated
A surge exceeding the rating of the SPD
has occurred.
Replace SPD and inspect other components for
damage and replace them if necessary.
Control Board LEDs do
not light.
Connection to P24 is loose or
disconnected.
Check the connection to P24 to verify that is
connected securely.
Check the connector from the transformer for loose
Check the connector from the transformer for loose
terminals.
Fuse located next to P24 has blown.
Verify that the fuses next to P24 have not blown.
Replace as needed.
24V transformer has failed.
With a voltmeter verify that the output from the
transformer is 24Vac ±10%. If the value exceeds
±
±
10%, verify that the correct primary leads are
being used.
Control Board (PEC/BEC) has failed.
If there is no output voltage, verify that the primary
connections are secure and receiving the correct
voltage. If they are, replace the transformer.
Fan will not run
Jumper not installed between 24V and
DIN1 (for Ziehl-Abegg fan motor).
Install jumper between 24V and DIN1 (for Ziehl
Abegg fan motor).