Emerson Liebert DS Precision Cooling System 28-105kW User Manual

Page of 32
Installation
10
2.3.1 Wire the Dampers
The damper wiring is coiled and attached to the interior of the Liebert Air Economizer. The locking 
connectors must be snapped into similar connectors in the primary cooling unit for the dampers to 
operate. The wiring must also be secured to the Liebert Air Economizer’s frame to protect it.
NOTICE
Turn Off all power to the indoor cooling unit before connecting cables or wires. Failure to do so 
may damage this equipment.
To connect the damper wiring:
1. Locate the damper wiring inside the Liebert Air Economizer—see Figure 5.
The wires are coiled and attached to the Liebert Air Economizer frame.
2. The wires have snap connectors that mate to wires secured to the cooling unit’s frame.
Figure 5
Damper wiring connections—Liebert DS and Liebert CW units
DETAIL A
DPN001449
Pg. 01, REV2
Return Air
Damper Motor
Connection
(Top Motor)
Outdoor Air
Damper Motor
Connection
(Bottom Motor)
Provide strain relief using
cable tie anchors as shown.
Confirm that the ties are
tightened to secure the
cable.
Cable Ties / Anchors
Route cable through
the loose cable tie on
the bottom plate of the
Liebert Air Economizer.
Tighten to provide strain relief.
Location of motor and unit control 
board depends on unit model