Emerson Liebert DS Precision Cooling System 28-105kW User Manual

Page of 32
Installation
12
Figure 7
Supply limit thermistor wiring and restricted airflow switch location
2.4
Adjust the Restricted Airflow Switch
The restricted airflow switch inside the cooling unit must be adjusted for the Liebert Air Economizer 
to operate properly and efficiently. To adjust the switch:
1. Inspect all connections, restore power to operate the unit’s blower.
2. Find the restricted airflow switch in the cooling unit (see Figure 7; the illustration shows the 
switch location in both the Liebert CW and Liebert DS units).
3. Turn On the Liebert DS or Liebert CW—the cooling unit must be running for the switch to be 
adjusted.
4. Turn the restricted airflow switch alarm setpoint knob clockwise until it trips. The cooling unit 
will also alarm.
5. Turn the setpoint knob counterclockwise:
a. half a turn for standard cooling units (about 75% airflow)
b. one full turn for cooling units equipped with a variable frequency drive (about 50% airflow)
c. or to the desired setpoint.
E
FRONT VIEW
120" Frame, Chilled Water
Restricted Airflow
Switch Location
Liebert DS + CW026-CW084
Restricted Airflow
Switch Location
P13 Factory-
Connected
Secure Supply Air Thermistor
In Airflow (120" Frame, Chilled
Water Location)
Secure Supply Air Thermistor
in Airflow (Liebert DS and
CW026-CW084 unit location)
P13 Factory-
Connected
DETAIL E
Restricted Airflow Switch
DPN001449
Pg. 05, Rev. 02
Restricted Airflow
Switch Alarm
Setpoint Knob
ADJUSTMENT INSTRUCTIONS:
1. Unit must be running.
2. Turn the adjustment knob clockwise
    until you hear it trip. Unit will also alarm.
3. Turn the adjustment knob back
    counterclockwise:
  - 1/2 turn for standard units
  - 1 turn for units with VFD
  - or to desired setpoint
Uncoil and
Extend Cable
Through Holes
Provided in
Bottom of Unit
Uncoil and
Extend Cable
Through Holes
Provided in
Bottom of Unit
Both po
ssible l
ow-volt
age
compar
tments 
shown.
Determ
ine whi
ch app
lies.
Locations for Liebert DS 
and Liebert CW units 
shown. Note location for 
your unit.