Installation and Configuration
16
5.2
External Battery Cabinet Installation
Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery 
run time. External battery cabinets are designed to be placed on one side of the UPS in a tower config-
uration or stacked beneath the UPS in a rack configuration. 
Figure 12 External battery cabinets connected to 6000VA Liebert GXT3
1. Inspect the external battery cabinet for freight damage. Report damage to the carrier and your 
local dealer or Emerson representative.
2. Optional rack-mount handles are shipped with the external battery cabinet and may be installed 
at this time if desired.
3. Securing hardware and slide rails are sold separately. Please contact your local dealer or 
Emerson representative for these additional options and any assistance needed. Fasten the slides 
into position with the screws per the instructions included with the slide rails.
4. Use the enclosed support bases for the tower option to prevent tip-over. One additional set of 
support base extensions ships with each external battery cabinet.
5. Put the UPS in Bypass Mode by pressing the bypass button on the front of the unit and holding it 
about 2 seconds.
6. Verify the External Battery Cabinet breaker is in the Off position.
7. Connect the supplied external battery cabinet cable to the rear of the external battery cabinet, 
then to the rear of the UPS.
8. Turn the External Battery Cabinet breaker to the On position.
9. Press the On button on the front of the UPS for 4 seconds to return the unit to Inverter Mode.
10. Verify the circuit breaker on the External Battery Cabinet is in the On position.
11. Use the included configuration program to program the UPS for the number of external battery 
cabinets connected. Instructions for the configuration program are in 6.0 - Configuration 
12. The UPS is now equipped with additional backup battery run time. For approximate battery run 
times, refer to Table 14.
!
WARNING
Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power supplies before working within.
Ensure that the Liebert
®
 GXT3
 is shut down and power has been disconnected before 
beginning any work on or in the unit.
!
CAUTION
The external battery cabinet(s) are heavy (see Table 11). Take proper precautions when 
lifting them.
NOTE
When removing the External Battery Cabinet, the circuit breaker on the rear of the cabinet 
must be turned off before disconnecting the cable.
Cable connects battery 
cabinet to 6000VA
Liebert GXT3
6000VA Liebert GXT3
Battery Cabinet
Second connector permits 
adding more battery cabinets 
to 6000VA Liebert GXT3