Fujitsu DX60S2 User Manual

Page of 62
Chapter 2  ETERNUS DX Disk Storage System Installation
  2.6  Circuit Protectors
ETERNUS DX60 S2 Disk storage system User’s Guide -Site Planning-
40
Copyright 2012 FUJITSU LIMITED
P3AM-5492-04ENZ0
For direct (no power distribution unit) connection
The breaking characteristics of distribution board circuit protectors must be slower than the val-
ues shown in 
 or equivalent to D (IEC898).
Figure 2.8
ETERNUS DX Disk storage system (PSU) breaking characteristics (graph)
Table 2.12 ETERNUS DX Disk storage system (PSU) breaking characteristics (Trip time (sec.))
Figure 2.9
Example of a power supply connection without power distribution units
Delay
100%
125%
150%
200%
400%
600%
800%
1000%
200E
No Trip
45 to 
500
15 to 
250
6 to
 90
0.7 to
 15
0.008 to
 5
0.006 to
 0.4
0.004 to
 0.08
CAUTION
Do
Only connect the ETERNUS DX Disk storage system to circuit 
protectors.
CURVE 200E
100
125
150
200
300
400
500
600
700
800
900
1000
1000
100
10
1
0.1
0.01
0.001
PERCENT LOAD (%)
TIME IN SECONDS
CE
P
S
U
P
S
U
DE #01
Line 0
Line 1
CP
CP
ETERNUS DX Disk storage system
T
o
 po
w
er supply f
acility
T
o
 po
w
er supply f
acility
Distr
ib
ution board
Distr
ib
ution board
CP: Circuit Protector
PSU
PSU
PSU
PSU