Fluke Digital Camera 1526 User Manual

Page of 41
MegOhmMeter
Specifications
31
Electrical Specifications
Battery
C Size 1.5 V alkaline, ANSI/NEDA-14A, IEC-
LR14 (4 pieces)
Fuse
6 mm x 32 mm (0.25 x 1.25 inch), 0.5 A 660 V,
Fast Acting, 50 A Minimum Interrupt rating
Insulation Resistance
Display Ranges
4.000 M
Ω
, 40.00 M
Ω
, 400.0 M
Ω
, 4000 M
Ω
Measurement Range (per EN61557-2)
0.250 M
Ω
 to 4000 M
Ω
Resolution
0.001 M
Ω
 to 10 M
Ω
2 % + 2 counts
0.250 M
Ω
 to 100.0 M
Ω
Accuracy
10 % + 2 counts + 1 %/1000 M
Ω
100.0 M
Ω
 to 4000 M
Ω
Analog Bar Graph
0 to