Commissioning
63
Performing a zero point adjustment
1.
Operate the system until operating conditions have settled.
2.
Stop the flow (v = 0 m/s).
3.
Check the shutoff valves for leaks.
4.
Check that operating pressure is correct.
5.
Now perform the adjustment as follows:
Key
Procedure
Display text
F
HOME position
→ enter the operating matrix
> GROUP SELECTION <
MEASURED VALUES
MEASURED VALUES
P
Select the "PROCESS PARAMETER" function group
> GROUP SELECTION <
PROCESS PARAMETER
PROCESS PARAMETER
N
Select the desired function "ZERO ADJUST".
ZERO ADJUST CANCEL
P
When you press
P you are automatically prompted to enter the access code if
the function matrix is still disabled.
CODE ENTRY
***
***
P
Enter code (80 = factory setting)
CODE ENTRY
80
80
F
Confirm code entry.
The "ZERO ADJUST" function then appears again on the display.
PROGRAMMING
ENABLED
ENABLED
ZERO ADJUST.
CANCEL
CANCEL
P
Select "START"
ZERO ADJUST.
START
START
F
Confirm entry with the E-key.
A security query appears on the display.
A security query appears on the display.
SURE? NO
P
Select "YES"
SURE? YES
F
Confirm entry with the E-key. Zero point adjustment is now started. The
message on the right appears on the display for 30 to 60 seconds while zero
point adjustment is in progress.
If the flow in the pipe exceeds 0.1 m/s, the following error message appears on
the display: "ZERO ADJUST NOT POSSIBLE".
message on the right appears on the display for 30 to 60 seconds while zero
point adjustment is in progress.
If the flow in the pipe exceeds 0.1 m/s, the following error message appears on
the display: "ZERO ADJUST NOT POSSIBLE".
When the zero point adjustment is completed, the "ZERO ADJUST." function
reappears on the display.
reappears on the display.
ZERO ADJUST.
RUNNING
RUNNING
ZERO ADJUST.
CANCEL
CANCEL
F
The new zero point value is displayed when the Enter key is pressed.
ZERO POINT
Q
Press
P simultaneously
→ HOME position