XR2500F Installation Guide
42
WIRInG dIaGRaMs
39.4  Prewired 866 Class B Style W Modules with Dual Notification Appliance Circuits
505-12 Power 
Supply
J6
 
+ DC -
AC 
Trouble
Batt 
Trouble
J4
J3
J2
Green 
LED 
AC 
AC 
+ BAT -
Red 
LED 
DC 
12 VDC @ 5 Amps
Battery 
Start
The Auxiliary Power Supply and Notification Circuit 
Module trouble contact zone must be programmed 
as a Supervisory Type zone and must be selected 
for display in the keypad status list. 
Auxiliary Power Supply must 
be Listed for Fire Protective 
Signaling Service.  Power 
Supplies must have battery 
backup. 
Listed, Polarized 
Notification Appliances
Model 308 
10K EOL
Sync module required when using 
multiple notification appliances
When using a separate power supply, the 
maximum current is 3 Amps.
See the Notification Appliance 
section for a list of appliances.
The maximum voltage drop 
between the panel Bell Output and 
the Model 308 is 1 VDC when a 
separate power supply is not used.
The Bell Output 
programming for Fire 
type zones must be set 
to Steady
Model 310 
1K EOL
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble
Normal/Silence Switch
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble
Normal/Silence Switch
DMP Model 866
45mA @ 12 VDC 
The 866 Notification 
Appliance  Circuit 
Module in alarm draws 
up to 31mA through 
its Terminal 3 Alarm 
Input and 45mA from 
its Terminal 1 Aux 
Power Input.
See the 866 
Installation (LT-0059) 
Prewired to XR2500F panel
Note:  If an 
auxiliary power 
supply is not used, 
Terminals 3 and 4 
jumper together to 
supply Bell Power 
from the panel
MINUS 2
MINUS 1
+OUT 1
+IN 1
+IN 2
-AUD
+AUD
+OUT 2
DSM-12/24 Module
Listed, Polarized 
Notification Appliances
Model 308 
10K EOL
See the Notification Appliance 
section for a list of appliances.
MINUS 2
MINUS 1
+OUT 1
+IN 1
+IN 2
-AUD
+AUD
+OUT 2
DSM-12/24 Module