DMP Electronics XR2500F User Manual

Page of 60
Digital Monitoring Products 
XR2500F Installation Guide
44
WIRInG dIaGRaMs
39.7  867 Class B Style W Multiple Notification Appliance Circuits
Model 310 
1K EOL
To initiating zone
Normal/Silence Switch
Ground Fault LED
Bell Trouble LED
Bell In +  1
Bell In -  2
Bell Out +  3
Bell Out -  4
Bell Trouble  5
Bell Trouble  6
PWR Mon.  7
Mon. RTN  8
TENS
ONES
TENS
ONES
Bell Relay 
Address
Supervisory 
Address
Bell Ring Style (Steady)
Power Supply Monitor LED
Data LED
505-12 Power 
Supply
J6
 
+ DC -
AC 
Trouble
Batt 
Trouble
J4
J3
J2
Green 
LED 
AC 
AC 
+ BAT -
Red 
LED 
DC 
12 VDC @ 5 Amps
Battery 
Start
The Auxiliary Power Supply and Notification 
Circuit Module trouble contact zone must be 
programmed as a Supervisory Type zone and 
must be selected for display in the keypad 
status list.  
Auxiliary Power Supply must be Listed for Fire 
Protective Signaling Service.  Power Supplies 
must have battery backup. 
LX-Bus Wiring
DMP Model 867
30mA @ 12 VDC 
The 867 must have its 
own independent 
address ranging from 
500 to 999.  A 
Supervisory zone must 
be programmed into the 
panel to properly 
supervise each module.
MINUS 2
MINUS 1
+OUT 1
+IN 1
+IN 2
-AUD
+AUD
+OUT 2
Model 308 
10K EOL
Listed, Polarized Notification Appliances
DSM-12/24 Module
Model 308 
10K EOL
See the Notification Appliance section 
for a list of appliances.
When using an DSM Sync Module, the 
maximum current is 3 Amps.
Sync module required when using 
multiple notification appliances