Delta Electronics DVPDNET-SL User Manual

Page of 32
DeviceNet Network Scanner DVPDNET-SL
 
DVP-PLC Application Manual 
25
Parameter 
Set value 
Explanation 
02-01 03 
The operation commands are operated on the communication 
interface. Operation by keys is valid. 
09-00 
01 
Communication address of VFD-B: 01 
09-01 
03 
Baud rate: 38,400 
09-04 
03 
Modbus RTU mode. Data format <8, N, 2> 
„ Explanations on devices 
Explanation 
PLC device 
Content
15 14 13 12 11 10 9
8  7  6  5  4
3
2
1
0
D6250 
0101Hex
ReqID = 01Hex 
Command = 01Hex 
D6251 
0005Hex
Port = 00Hex 
Size = 07Hex 
D6252  0E02Hex
Service Code = 10Hex 
MAC ID = 02Hex 
D6253 
0099Hex
High byte of Class ID = 00Hex  Low byte of Class ID = 99Hex
D6254 
0001Hex
High byte of Instance ID = 
00Hex 
Low byte of Instance ID = 
01Hex 
D6255 
0002Hex
N/A 
Attribute ID = 02Hex 
Request 
message 
editing area 
D6256 
0004Hex
High byte of data = 00Hex 
Low byte of data = 04Hex 
D6000 
0101Hex
ReqID = 01Hex 
Status = 01Hex 
D6001 
0002Hex
Port = 00Hex 
Size = 02Hex 
D6002 
9002Hex
Service Code = 90EHex 
MAC ID = 02Hex 
Response 
message 
editing area 
D6003 
0004Hex
High byte of Service Data = 
00Hex 
Low byte of Service Data = 
04Hex 
(3) PLC 
program 
MOV
H0101
D6250
M1002
ZRST
D6250
D6281
M1
MOV
H0008
D6251
MOV
H0E02
D6252
MOV
H0099
D6253
MOV
H0001
D6254
MOV
H0002
D6255
ZRST
D6000
D6031
Reset response message editing area
& request message editing area
ReqID = 01, Command = 01
Port = 00, Size = 08
Service Code = 0E, MAC ID = 02
Class ID to be write= 99
Instance ID to be 
 = 01
written
Attribute ID to be 
 = 02
written
MOV
H0004
D6256
Data to be written = 0004
 
(4) Program 
explanations 
„ In the beginning of the program, clear the response message editing area and request message