Delta Electronics DVPDNET-SL User Manual

Page of 32
DeviceNet Network Scanner DVPDNET-SL
 
DVP-PLC Application Manual 
27
Corresponding nodes on the network 
PLC 
device 
b15 
b14 
b13 
… 
b1 
b0 
D6032 
Node 15 
Node 14 
Node 13 
… 
Node 1 
Node 0 
D6033 
Node 31 
Node 30 
Node 29 
… 
Node 17 
Node 16 
D6034 
Node 47 
Node 46 
Node 45 
… 
Node 33 
Node 32 
D6035 
Node 63 
Node 62 
Node 61 
… 
Node 49 
Node 48 
When the node in the scan list is normal, the corresponding bit will be Off. If the node occurs abnormality, its 
corresponding bit will be On.
 
8.2 
Status of DVPDNET-SL 
You can acquire the real-time status of DVPDNET-SL by monitoring D6036. When DVPDNET-SL runs 
normally, D6036 = 0. When DVPDNET-SL is being initialized, the high byte of D6036 = 1 and the low byte = 0. 
When error occurs in DVPDNET-SL, the high byte of D6036 = 2. The low bytes are for error codes. For detailed 
information on error codes, please refer to 9.5. Digital Indicator LED.
 
Explanation 
PLC 
device 
b15  b14  b13  b12  b11 b10
b9
b8
b7
b6
b5
b4
b3 
b2 
b1 
b0
D6036 
Status of DVPDNET-SL 
(0: normal, 1: initializing, 2: error) 
Error codes of DVPDNET-SL 
(See 9.5) 
LED Indicator & Trouble-shooting 
There are three LED indicators and one digital indicator on DVPDNET-SL. POWER LED displays if the 
power of DVPDNET-SL is working normally; NS LED and MS LED display the communication connection status 
of DVPDNET-SL; digital indicator displays the node addresses, error information and the error messages from 
the slave.
 
DVPDNET
POWER
MS
NS
 
9.1 POWER 
LED 
LED status 
Indication 
How to correct 
Off 
Power is abnormal. 
Make sure DVPDNET-SL is powered. 
Green light on 
Power is normal. 
-- 
9.2 NS 
LED 
LED status 
Indication 
How to correct 
Off 
No power or duplicate ID 
check has not completed 
1. Make sure DVPDNET-SL is powered. 
2. Make sure at least 1 node or more are 
communicating on the network. 
Green light 
blinking 
No communication 
No correction is needed, or check the digital indicator 
for the error. 
Green light on 
Normal operation 
--