Bosch Appliances Smoke Alarm D1257RB User Manual

Page of 14
D1255RB/D1256RB/D1257RB | Installation Instructions | 4.0  D1256RB Programming Requirements 
 
Bosch Security Systems, Inc. | 8/06 | F01U011791B 
11 
 
4.4.1 
Menu Item and Function 
Program the first ten menu items as indicated in 
Table 3. This programming is necessary for the 
D1256RB to operate properly. The first four keys on 
the D1256RB execute the first four menu items 
enabled at the keypad address. Menu items five 
through ten are optional features that can be 
programmed into the D1256RB system. Refer to the 
Fire System User’s Guide (P/N: F01U011793) for further 
explanation of these optional programmable items. 
 
 
Ensure that CF 128 through CF 131 are 
programmed E (enabled) and not P 
(passcode required). 
 
 
Table 3: 
Function List Description 
 
Menu Item 
Function 
Description 
128 
ALARM SILENCE? 
2 129 
TROUBLE SILENCE? 
130 
DETECTOR RESET? 
4 131 
ANNUNCIATOR RESET 
VIEW MEMORY? 
6 10 
VIEW PT STATUS? 
12 
FIRE TEST? 
8 21 
VIEW LOG? 
29 
REMOTE PROGRAM? 
10 32 
DISPLAY REV? 
 
4.4.2 
CC Address # 
 
CC = command center = keypad 
Program the keypad (command center) addresses as 
Yes for the first four menu items and for the optionally 
programmed menu items five through ten. 
 
4.4.3 Passcode 
Worksheet 
 
Figure 17:  Example – Fire Passcode Worksheet 
User (Passcode) Worksheet (Users 000 to 029) 
 
 
Area Authority 
 
User 
##
Passcode 
User 
Group 
User Name 
000 
123 __ __ __ __ __ __
 
____ 
15 
15 
15 
15 
15 
15 
15 
15 
SERVICE 
PASSCODE 
 
001 
1 2 5 6 0 0 
____ 
 14 
__ __ __ __ __ __ __ 
USER 1 
 
 
 
Refer to User (Passcode) Worksheet in the program record sheet for the control panel. 
4.4.4 Passcode 
A special passcode must be programmed as a valid passcode for the system to work properly. This passcode is 
used in Custom Functions 128 through 131. Use any user number to establish this mandatory valid passcode. You 
must also create it as a valid passcode in the area to which the D1256RB is assigned. Use Authority Level 14 
together with the passcode you select. Ensure that 
Passcode Arm is disabled (blank) for the Authority Level. 
Refer to Authority Level Selections in the program record sheet for the control panel.