Bosch Appliances Network Router D6100 User Manual
Conettix D6600/D6100 | Computer Interface Manual | 3.0
Computer Communication Protocols
22
Bosch Security Systems, Inc. | 1/07 | 4998122703-01
3.1.22 Silent Knight FSK0 (Message Type 1)
D6500 Byte Description
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20 21 22
Silent Knight
FSK0 Example
FSK0 Example
h 1 r r l s s s s s s a a a a s E s s s Z t
Table 25:
Silent Knight FSK1 (Message Type m) Byte Description
# Title
Description
1
Header Character
(
(
h
)
Optional. Check with the computer automation software for compatibility.
2
Message Type
1
3-4
Receiver Number
Receiver gateway number from 01 to 99.
5 Line/Group
Number
Line number in the receiver gateway that sent the message.
6-11
Spaces
Six spaces.
12-15 Account
Number
Four digit account number.
16
Spaces
One space.
17 E
Event code.
18-20
Space
Three spaces.
21 Zone
number
Zone number.
22
Trailer Character
Typically, HEX 14.
Optional Silent Knight SK1 (Message Type m):
If Menu Item 2.5.16 in the D6600/D6100 Receiver is equal to 1, the following output is used.
D6500 Byte Description
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20 21 22
Silent Knight
FSK1 Example
FSK1 Example
h m r r l s a a a a a a a a “ Z Z “
. . .
t
Table 26:
Optional Silent Knight SK1 (Message Type m) Byte Description
# Title
Description
1
Header Character
(
(
h
)
Optional. Check with the computer automation software for compatibility.
2
Message Type
m
3-4
Receiver Number
Receiver gateway number from 01 to 99.
5 Line/Group
Number
Line number in the receiver gateway that sent the message.
6
Spaces
One space.
7-14
Account Number
Maximum eight-digit account code. If the account code is less than eight digits, enter the
actual number of digits without a leading space.
actual number of digits without a leading space.
15
“
Separator.
16-17 ZZ
First zone number, up to eight reports, one report has two digits.
18
“
Separator.
19
***
More data.
21
Trailer Character
Typically, HEX 14.