Bosch Appliances Home Security System ICP-CC404 User Manual

Page of 98
ICP-CC404 | Installation Guide | 17.0   System Event Timers 
 
 
Bosch Security Systems, Inc. | 12/08 | F01U089401-02 
71
 
You can program Entry Timer 1 from 0 to 255 sec in 
increments of 1 sec. Entry Timer 1 is the delay time 
used by the Delay-1 Zones. Refer to Section 14.3.1 
Zone Types
 on page 55 for more information.  
17.3  Entry Timer 2 
Program Entry Timer 1 into 
Locations 400 
(increments of 1 sec) and 
401 (increments of 16 sec). 
The default value for Entry Timer 2 is 40 sec (
8  2). 
You can program Entry Timer 2 from 0 to 255 sec in 
increments of 1 sec. Entry Timer 2 is the delay time 
used by Delay-2 Zones. Refer to Section 14.3.1 Zone 
Types
 on page 55 for more information. 
17.4 Exit 
Time 
Program Exit Timer into 
Locations 402 (increments 
of 1 sec) and 
403 (increments of 16 sec). 
The default value for the Exit Timer is 60 sec (
12  3). 
You can program the Exit Timer from 0 to 255 sec in 
increments of 1 sec. When arming the system in 
AWAY Mode, the remote codepad beeps during Exit 
Time until the final 10 sec, when the codepad sounds 
one continuous beep to indicate the end of Exit Time 
is near. 
The remote codepad always sounds one short beep at 
the end of Exit Time when arming in STAY Mode 1 
or STAY Mode 2. 
17.5  Entry Guard Timer for STAY Mode 
Program Entry Guard Timer for STAY Mode into 
Locations 404 (increments of 1 sec) and 405 
(increments of 16 sec).  
The default value for Entry Guard Timer for STAY 
Mode is 
0. 
Entry Guard Timer for STAY Mode is the delay time 
used for all zones except 24-Hour Burglary and 24-
Hour Fire Zones when the system is armed in STAY 
Mode 1 or STAY Mode 2. All zones, including Delay 
Zones, use this timer for the entry delay (for example, 
the Entry Guard Timer overrides the delay time 
programmed for a Delay Zone). If the Entry Guard 
Timer is programmed as 0, each zone acts according 
to its programmed zone type. 
17.6  Delay Alarm Reporting Time 
Program the Delay Alarm Reporting Time into 
Locations 406 (increments of 1 sec) and 407 
(increments of 16 sec). 
The default value for the Delay Alarm Reporting 
Time is
 0. 
These locations program the time in sec that a 
delayed report waits dormant in the dial buffer before 
it is sent to the receiving party. If a User Code holder 
resets the alarm within this time frame, the control 
panel clears the dialer buffer and does not report the 
alarm to the receiving party. Refer to Section 14.3.4 
Zone Options 1
 on page 57 to program zones for delay 
alarm reporting. 
17.7  Sensor Watch Time 
Program Sensor Watch Time into 
Locations 408 
(increments of days, tens digit) and 
409 (increments of 
days, units digit). 
The default value for the Sensor Watch Time is
 0. 
The time set in these two locations determines the 
number of days (0 to 99) a zone can remain sealed 
before registering as a fault. This feature is active only 
when the system is disarmed. If a zone programmed 
for Sensor Watch is not unsealed and reset during this 
time, the FAULT indicator lights. Refer to Section 4.13 
Fault Descriptions
 on page 22 for more information on 
Sensor Watch Faults. Refer to Section 14.3.4 Zone 
Options 1
 on page 57 for programming zones for 
Sensor Watch. 
The Sensor Watch Time counter is active only when 
the control panel is disarmed. If the system is 
disarmed for 8 hours a day and the Sensor Watch 
Time is programmed for 1 day, a zone programmed 
for Sensor Watch registers a Sensor Watch Fault if it 
is not activated while disarmed within 3 days. 
This feature is useful, for example, when someone 
places objects in the view of a motion detector, 
preventing the detector from picking up movement.  
17.8  Codepad Lockout Time 
Program the Codepad Lockout Time into 
Location 410 (increments of 10 sec). 
The default value for the Code Lockout Time is 
0. 
All codepads are locked out for the programmed time 
if an invalid code is entered more times than allowed 
by the code retry attempts programmed in 
Location 356 (refer to Section 15.19 System Status – 
Access Denied
 on page 63). If the Codepad Lockout 
Time is programmed as 0, codepad lockout does not 
occur. 
17.9 Siren 
Run 
Time 
Program the Siren Run Time into Location 411 
(increments of 1 minute). 
The default value for the Siren Run Time is 
5. 
The Siren Run Time determines how long the horn 
speaker operates during an alarm. You can program 
the Siren Run Time from 0 to 15 min. 
17.10 Siren Sound Rate 
Program the Siren Sound Rate into 
Location 412. 
The default value for the Siren Sound Rate is 
7.