ICP-CC404 | Installation Guide | 17.0   System Event Timers 
 
 
72 Bosch 
Security 
Systems, 
Inc. | 12/08 | F01U089401-02
 
The Siren Sound Rate varies the frequency of the 
siren tone slowest (0) and to fastest (15). The Siren 
Sound Rate does not change the frequency of the fire 
alarm tone. 
17.11  Auto Arming Pre-Alert Timer 
Program the Auto Arming Pre-Alert Timer into 
Location 413 (increments of 5 min). 
The default value for the Auto Arming Pre-Alert 
Timer is 
1 (5 min). 
This location sets the time period during which the 
control panel warns you it is automatically armed in 
AWAY Mode. The codepad beeps once every second 
until the Pre-Alert Timer expires: the system then 
automatically arms itself in AWAY Mode. If you 
want the system to automatically arm in STAY Mode 
1, select Option 4 in Location 428 (refer to Section 
18.5 Consumer Options 1
 on page 75). 
After the control panel automatically arms in AWAY 
Mode or STAY Mode 1, Exit Time starts. If a valid 
User Code is entered during the Pre-Alert Time, the 
Auto Arming Time programmed in Locations 414 to 
417 (refer to Section 17.12 Auto Arming Time) is 
extended by 1 hour. 
If you want a programmable output to operate during 
the Auto Arming Pre-Alert Time, use Output Event 
Type 0,5 Auto Arm Pre-Arming Alert Time (refer to 
page 65). 
17.12  Auto Arming Time 
Program the Auto Arming Time in 
Locations 414 to 
417 as described in Table 58
The default value is midnight (
0  0  0  0). 
 
Table 58: 
Auto Arming Time Parameters  
 
Location Parameter 
Default 
414 
Hour of day (tens digit) 
415 
Hour of day (units digit) 
416 
Minute of day (tens digit) 
417 
Minute of day (units digit) 
 
These locations specify the time of the day that the 
system automatically arms itself in AWAY Mode. Set 
this time in 24-hour format (for example, program 
10:30 PM as 2230). If you want the system to arm in 
STAY Mode 1, select Option 4 in Location 428 (refer 
to Section 18.5 Consumer Options 1 on page 75).   
If forced arming is disabled for any zone, the 
automatic arming feature operates regardless of 
whether any zones are unsealed. Refer to Section 
14.3.6 Zone Options 2
 on page 58 for more information 
on programming zones for forced arming. 
User Code 16 is reported when this feature is used. 
17.13  Auto Disarming Time 
Program the Auto Disarming Time in 
Locations 418 
to 
421 as described in Table 59
The default value is midnight (
0  0  0  0). 
 
Table 59: 
Auto Disarming Time Parameters  
 
Location Parameter 
Default 
418 
Hour of day (tens digit) 
419 
Hour of day (units digit) 
420 
Minute of day (tens digit) 
421 
Minute of day (units digit) 
 
These locations specify the time of day that the 
system automatically disarms itself. Set this time in 
24-hour format (for example, program 10:30 PM as 
2230).   
User Code 16 is reported when this feature is used. 
 
 
17.14  Kiss-Off Wait Time 
Program the Kiss-Off Wait Time into 
Location 422 
(increments of 500 millisec). 
The default value for the Kiss-Off Wait Time is 
(1500 ms). 
This location sets the time that the control panel waits 
for acknowledgment before resending a report. This 
timer applies only to the 4 + 2 Express Format. 
17.15 System Time 
Program the System Time in 
Locations 901 to 904 as 
described in Table 60
The default value is 
0  0  0  0. 
 
Table 60: 
System Time Parameters  
 
Location Parameter 
Default 
901 
Hour of day (tens digit) 
902 
Hour of day (units digit) 
903 
Minute of day (tens digit) 
904 
Minute of day (units digit) 
 
The ICP-CC404 Control Panel has a real-time 
24-hour clock you must set during installation. Set 
this time in 24-hour HHMM format (for example, 
program 10:30 PM as 2230). You must reset the 
System Time every time power is removed from the 
system. 
A Master Code holder can also set the System Date 
and Time (refer to Section 6.2.7 Setting the Date and 
Time
 on page 36). 
17.16 System Date 
Program the System Date in 
Locations 905 to 910 as 
described in Table 61
The default value is 01 January, 2001 (
0  1  0  1  0  1).