D9112B | Program Entry Guide | 10.0  Skeds 
EN | 92 
 
 
Bosch Security Systems | 2/04 | 74-06145-000-D 
 
 
Default  Description 
Sub-prompt 
Selection 
14 
Adjust Time Backward One Hour. This Sked function is used to make adjustments to the panel’s 
clock. A typical application is to program this to take effect at 2:00 a.m. on the date that Daylight 
Savings Time ends (during the fall). This function can operate only once in a day, even if multiple 
Skeds with this function are programmed. No 
Time
 
Change
 
report is sent or logged, but the new 
time appears in the next report logged. 
15 
Sound Watch Tone at Command 
Center. This function sounds the 
Watch Tone at the command center 
address programmed. The Watch 
Tone sounds at all command 
centers set for the address 
programmed. Press [ESC] to silence 
the tone. 
Sound Watch Tone. Defines the 
command center address where the 
Watch Tone sounds.
 
S## Cmd Center
 
 
Enter a command center 
address, 
1 to 8. 
 
 
S## Time 
Default: 
_ _:_ _ 
Selection: 
HH:MM (hours and minutes) 
Enter the time the Sked executes. 
0101
0101
0101
 
 
Disabled Skeds have a Blank time. If you 
copy the panel and the entry for this prompt 
is blank, but times were at one time 
programmed, the Sked may have been 
disabled from the command center using 
the CHANGE SKEDS function. 
To program a time: 
1.  Press the two digits representing the hour. 
2.  The cursor advances past the colon (:) in the 
display. 
3.  Press the two digits representing the minutes. 
4. Press 
[ENT]. 
S## Date 
Default: 
_ _/_ _ 
Selection: 
MM/DD or Blank 
This entry selects the month and day that the Sked 
operates (Date of the Year, Sked Type 1). 
Leave this item blank if this Sked operates on a Day 
of the Week schedule. 
To program a date: 
1.  Press the two digits representing the month. 
2.  The cursor advances past the (/) in the display. 
3.  Press the two digits representing the day of the 
month. 
4. Press 
[ENT]. 
S## Sunday 
This prompt and the next six-day of the week 
prompts, select the days of the week that the Sked is 
active. (Day of Week, Sked Type 2). 
Exceptions: To prevent the Sked from activating on 
certain days of the year, program 
Xept Holiday
 
YES, and enable at least one Holiday Index. When 
Xept Holiday
 is programmed YES, the window 
executes on the days of the week programmed 
unless the date is designated as a holiday by the 
Holiday Index selected. 
If a Sked is only needed on certain days of the year, 
do not program the Sked to execute on any days of 
the week. Instead, program 
Xept Holiday
 NO, and 
select a Holiday Index with the dates you want the 
window to be active. 
Default: 
No 
Selection: 
Yes or No 
Yes 
Activate this Sked on Sundays. 
No 
Do not activate this Sked on Sundays.