Bosch Appliances Home Security System D9412GV2 User Manual

Page of 74
D9412GV2/D7412GV2 | Operation and Installation Guide | 9.0  Off-Board Points 
 
Bosch Security Systems, Inc. | 5/05 | F01U003641B 
41 
 
The D8128D is also suitable for fire supervisory 
applications, such as indicating circuit supervision 
(using the D192C/D192G Bell Circuit Supervision 
Module), sprinkler supervision, and valve tamper 
protection.  
Requirements for Fire Initiation Applications 
 
 
Non-powered, fire initiating devices such as 
pull-stations, heat detectors, and UL Listed 
four-wire smoke detectors can be connected 
directly to the point inputs on the D8128D. 
The D125B Dual Powered Loop Interface Module or 
the D129 Dual Class “A” Module zone outputs can be 
connected directly to the point inputs on the D8128D. 
Use the D125B to connect two-wire smoke detectors. 
Typically, the D129 is used for connecting waterflow 
switches. 
The D125B or D129 and the OctoPOPIT can be 
mounted in the same enclosure with the control panel 
or in a separate enclosure connected to the control 
panel’s enclosure by a conduit not more than 6 m  
(20 ft.) in length. 
Figure 15:  D8128D OctoPOPIT Layout 
2 3 4 5
1
6 7 8
P O I N T S
1
2
3
4
 
1 -  Molex
®
 connectors 
2 -  Address DIP switches 
3 -  Terminal strip 
4 -  Point DIP switches 
9.4.3 Installation 
For the most effective installation, use the following 
four-step process: 
1.  Set the OctoPOPIT switches. Refer to Section 9.4.4 
Setting the OctoPOPIT Switches
2.  Physically mount the OctoPOPIT in the enclosure. 
Refer to Section 9.4.5 Mounting OctoPOPITs, page 42. 
3.  Wire the OctoPOPIT. Refer to Section 9.4.6 Wiring 
OctoPOPITs on page 42. 
4.  Wire the OctoPOPIT sensor loops. Refer to Section 
9.4.7 OctoPOPIT Sensor Loops on page 46. 
9.4.4 
Setting the OctoPOPIT Switches 
The D8128D OctoPOPIT has two sets of DIP switches 
(Figure 15). Use the DIP switches on the top of the unit 
(with the terminal strip along the left edge) to set the 
address for the OctoPOPIT. Use the DIP switches at 
the bottom of the unit to enable or disable individual 
points connected to the OctoPOPIT. 
Address Switches 
The switches on the D8128D OctoPOPIT set point 
assignments and line termination. These switches are 
easier to set before mounting the D8128D in the 
enclosure. 
Switches 1, 2, 3, and 4 assign the OctoPOPIT sensor 
loops to point numbers on the control panel. Table 15 
on page 42 shows the OctoPOPIT switch settings for 
point assignments. 
Switch 5 sets line termination. Refer to Table 16 on 
page 42.