D9412GV2/D7412GV2 | Operation and Installation Guide | 9.0   Off-Board Points 
 
42 
Bosch Security Systems, Inc. | 5/05 | F01U003641B 
 
Table 15: 
D8128D OctoPOPIT Switch Settings 
for D9412GV2 and D7412GV2 
 
ZONEX 1 
D8128D Address Switches 
ZONEX 2 
Points 9 to 
127 
1 2 3 4 5 
Points 129 
to 247 
9 to 16 
ON 
ON 
ON 
ON 
129 to 136 
17 to 24 
ON 
ON 
ON 
OFF 
137 to 144 
25 to 32 
ON 
ON 
OFF 
ON 
145 to 152 
33 to 40 
ON 
ON 
OFF 
OFF 
153 to 160 
41 to 48 
ON 
OFF 
ON 
ON 
161 to 168 
49 to 56 
ON 
OFF 
ON 
OFF 
169 to 176 
57 to 64 
ON 
OFF 
OFF 
ON 
177 to 184 
65 to 72 
ON 
OFF 
OFF 
OFF 
185 to 192 
73 to 80 
OFF 
ON 
ON 
ON 
193 to 200 
81 to 88 
OFF 
ON 
ON 
OFF 
201 to 208 
89 to 96 
OFF 
ON 
OFF 
ON 
209 to 216 
97 to 104 
OFF 
ON 
OFF 
OFF 
217 to 224 
105 to 112 
OFF 
OFF 
ON 
ON 
225 to 232 
113 to 120 
OFF 
OFF  
ON 
OFF 
233 to 240 
121 to 127 
OFF 
OFF 
OFF 
ON 
241 to 247 
Line Termination Switch 
 
 
 
For the D8128D OctoPOPITs assigned to 
Points 121 to 127, 241, and 247, set Point 
Input Switch 8 to the OPEN position. 
D9412GV2 uses Points 9 to 127 on Zonex 
1 and Points 129 to 247 on Zonex 2. 
D7412GV2 uses Points 9 to 75 on Zonex 1 
only. 
 
Table 16: 
Switch 5 Settings for Line Termination 
 
Is a D8125 
POPEX Module 
connected? Zonex 
No. 
Switch 5 Setting(s) on 
D8128D OctoPOPIT(s) 
No 
NA 
Set Switch 5 of only 
one D8128D to ON 
Yes 1 
Set Switch 5 of all 
D8128Ds to OFF 
No 
NA 
Set Switch 5 of only 
one D8128D to ON 
Yes 2 
Set Switch 5 of all 
D8128Ds to OFF 
Point DIP Switches 
Each point connected to the D8128D is enabled by 
closing the respective DIP switch, or disabled by 
opening the DIP switch. For example, to disable a 
device connected to the P3 Terminal (Point 3), move 
DIP switch number 3 to the OPEN position. 
Use the point DIP switches to disable conflicting 
points, such as when a D9210B Access Control Module 
must be assigned to a point that falls within the range 
of the D8128D OctoPOPIT. In this example, a 
D9210B is assigned to Point 20. On the same system, a 
D8128D OctoPOPIT is assigned to Points 17 through 
24. Moving the DIP switch for Point 4 to the OFF 
position would effectively disable Point 20, allowing 
normal operation of the D9210B and the OctoPOPIT. 
Terminate each OctoPOPIT sensor loop with a 1 k
Ω
 
EOL resistor. Attach a resistor even if you do not 
enable the loop. 
9.4.5 Mounting 
OctoPOPITs 
The D8128D OctoPOPIT Module can be installed in 
the enclosure with the control panel using standard 
four-conductor 0.8 mm (22 AWG) wire, or in a 
separate enclosure (Model D8103, D8103A, or D8109) 
up to 61 m (200 ft.) from the control panel using 
shielded (recommended) standard four-conductor  
0.8 mm (22 AWG) wire. If using the D125B or D129, 
refer to the Specifications section of the D8128D 
Installation Guide
 (P/N: 41323) for cabling 
requirements. 
For UL Listed systems, mount the D8128D in a 
tamper-proof enclosure. To install OctoPOPITs in the 
control panel’s enclosure, complete the following 
procedure. Use the D137 Mounting Bracket to install 
OctoPOPITs in enclosures with no module-mounting 
locations available. 
1.  Align the OctoPOPIT module using any of the 
four mounting locations in the enclosure. Refer to  
Figure 2 on page 15. 
2.  Use the screws provided with the module to secure 
it in the enclosure. 
9.4.6 Wiring 
OctoPOPITs 
 
Warning: Disconnect all power to the 
control panel before beginning any work 
with the internal components. Serious injury 
could result from electrical shock. 
1.  Power down the control panel: 
a.
 
Disconnect the positive (red) battery lead at 
the battery. 
b.
 
Unplug the transformer.