D9412GV2/D7412GV2 | Operation and Installation Guide | Appendix A: System Wiring Diagrams, Issue A 
 
Bosch Security Systems, Inc. | 5/05 | F01U003641B 
67 
 
A.2 
D7412GV2 Control Panel 
 
Figure 37:  D7412GV2, Power Supply Side 
+
AUX PWR
ALARM TRIG
COM
SUPV IN
ALARM CKT
D192C/G
-
D928
D8132
D113
BAT 2+
BAT 1+
BAT 2-
BAT 1-
SUPV
CHGR+
CHGR-
VAUX+
EARTH GROUND
COMMON
BATTERY NEGATIVE ONLY
Maximum Charging
Current 1.4 Amps.
BATTERY POSITIVE ONLY
RELAY A
RELAY B
RELAY C
+ AUX POWER
CLASS 2 TRANSFORMER
16.5 VAC 40 VA 60 Hz
Model D1640
Internally Fused - Do Not short
Requires Unswitched Outlet
Do Not Share With Other Equipment
PROGRAMMABLE
ALARM OUTPUTS
Terminals
Requires Optional
Model D136 Relay
In ALT ALARM
& SW AUX
&
7
8
GROUND FAULT DETECT
Enabled
Disabled
12
11
13
Point 1 Point 2
15
14
16
Point 3 Point 4
D1640
16.5 V, 40 VA
60 Hz
C900
D126
Battery
12 V, 7 Ah/
D1218
12 V, 17.2 Ah
or 18.0 Ah
D126/
D1218
D126/
D1218
D126/
D1218
D126/
D1218
D126
Battery
12 V, 7 Ah/
D1218
12 V, 17.2 Ah
or 18.0 Ah
D7412GV2
PHONE
LED
RED
ON when
communicating
OFF when idle
PHONE LINE SEIZED
TIP
RING
TELCO
 
1 -  If required by local AHJ, connect D113 Battery 
Lead Supervision Module. 
2 -  D122 Dual Battery Harness, as required. 
3 -  D1640 Transformer and D8004 Transformer 
Enclosure required for NFPA Applications 
4 -  D8132 Dual Battery Charger with two batteries 
(batteries are not supervised) 
5 -  Power limited, supervised 
6 -  Power limited 
7 -  To Relay A or Relay B 
8- 
Listed Audible Signaling Devices rated at 10.2 
to 13.8 VDC (Do not use vibrating type horns.) 
9- Optional 
10- 560 
Ω
, 2 
Ω
 EOL Resistor (P/N: 15-03130-005) 
11-  RJ31X, Secondary phone line 
12- RJ31X, Jack 
13-  RJ31X, Primary phone line 
14-  To earth ground