Bosch Appliances Home Security System D7212G User Manual

Page of 68
D7212G Operation and Installation Guide
D7212G
Page 13
© 2003 Bosch Security Systems
4998138544C
Overview
2.0
Overview
Use command centers and/or keyswitches to arm the
panel by area. Each panel can have up to four areas.
Each area can have its own account number or areas
can be grouped together with a common account
number. Points of protection are assigned to areas.
Control/
Communicator
On-Board Points
1 to 8
D9131A Module connects
to a parallel printer to print
the event log.
D9133TTL-E allows communication
over a Local or Wide Area network.
D8129 OctoRelay provides alarm
and auxilliary relay output.
(Other functions available.)
D8125 or D8125MUX Interface
used for point expansion.
Each D8128D OctoPOPIT combines
eight POPIT points in one module.
D8132 Modules (two 12 VDC, 7Ah batteries)
provide additional power for command
 centers and other powered devices.
Figure 1: System Configuration
2.1
9000G Series Panel Differences
Table 3 provides an overview of the differences between the D9412G, D7412G, and D7212G Panels.
New Features
D9412G
D7412G
D7212G
Access Control
YES, 8 Doors
YES, 2 Doors
NO
Expanded Users
Arm/Disarm Passcodes
Cards/Tokens
249
996
99
396
99
N/A
Passcode-Protected Custom Functions
16
4
4
Number of Printers
3
1
1
Number of Points
246
75
40
Number of Relays
128
64
24
Table 3: Differences between the 9000G Series Panels