Bosch Appliances Home Security System D7212G User Manual

Page of 68
D7212G Operation and Installation Guide
D7212G
Page 23
© 2003 Bosch Security Systems
4998138544C
Releasing the reset pin from the closed position resets the panel. The panel resets all its timers, counters, indexes, and buffers.
Any points that restore after a reset is performed will not generate restoral reports.
If the reset pin is placed in the disable position when all areas are armed, there must be an entry in the Answer Armed
program item. See RAM Parameters in the D7212G Program Entry Guide (P/N: 4998138538).
Locking the pin in the disable position allows powering up the panel and charging the battery while the detection devices and
command centers are being installed.
3.6
Finishing the Installation
Earth ground and reset pin first: Make the earth ground connection to Terminal 10 and lock the reset pin in the closed
position if not already done.
3.6.1
Charge the Battery While Finishing
Connect the battery and then the transformer so that the panel can charge the battery while the installation is being finished.
See Section 4.0 Power Supply, on page 25 for instructions.
On-board Buzzer Sounds at Power Up and Reset: The system performs a series of self diagnostic tests of its hardware,
software, and program at power up and at reset. The buzzer on the panel sounds during the tests. The self diagnostics take
about 1-3 seconds to complete.
If the panel fails any of the tests, the buzzer continues sounding and a system trouble message appears at the command
centers. See Problems Found During Self Diagnostics in the D9412G/D7412G/D7212G Installation and Troubleshooting Quick
Reference Guide 
(P/N: 43700) for a description of each system trouble message.
Touch Terminal 10 first: If the on-board buzzer sounds briefly when the panel is touched, any static charge that may be
carried is being discharged to the panel. The panel may generate 
WATCHDOG RESET
 and/or 
PARAM FAIL
 events. See the
Watchdog Reset Reports section in the D9412G/D7412G/D7212G Installation and Troubleshooting Quick Reference Guide
(P/N: 43700) for a description of these events. Always touch Terminal 10, the panel's earth ground connection, before
beginning work on the panel.
3.6.2
Install and Wire Detection Devices
Install and wire detection devices and command centers at their locations throughout the premises. DO NOT make the
connections at the panel end of the wiring yet.
Section 7.0 On-board Points on page 35 contains instructions for wiring the on-board points to detection devices. Section 10.0
Arming Devices,
 beginning on page 49, contains instructions for wiring the command centers.
Instructions for wiring the off-board point POPIT sensor loops are found in the instructions packaged with the POPIT
Modules.
3.6.3
Install Modules and Relays
1.
Power Down First: Power down the unit by unplugging the transformer and disconnecting the battery. Bosch
Security Systems recommends powering down the unit when installing modules or relays, or when making
wiring connections to the panel.
2.
Install and wire any modules required for the installation as described in the module’s installation instructions.
Instructions for the D8125 POPEX Module, the D8128D OctoPOPIT Module, and the D8129 OctoRelay
Module appear in this guide.
See Section 8.0 Off-board Points on page 37 for D8125 and D8128D instructions. See Section 9.0 Off-board Relays
on page 47 for D8129 instructions.
3.
If using the power outputs at Terminals 7 or 8, install a D136 relay in the appropriate sockets. See Section 5.4
Programmable Power Outputs Terminals
 on page 29 for instructions.
4.
If using a ground start phone system, insert a D136 relay in the ground start check socket and set the ground
start pin in the ground start position. See Section 6.11 Ground Start on page 33 for more information.
Installation