Bosch Appliances Home Security System D7212G User Manual

Page of 68
D7212G Operation and Installation Guide
Page 42
© 2003 Bosch Security Systems
4998138544C
D7212G
Off-board Points
POPIT Labels
Off-board points for the D7212G are numbered 9 to 40.
Two sheets of peel-off POPIT labels are supplied with the D8125 POPEX Module. Use the sheet marked Bank1 for Points 9 to
40.
Each label has two parts. Place the smaller part, with just the point number on it, on the chip. Place the larger part with the
switch settings on the base of the POPIT. Set the switches and cover the POPIT.
Do not program two POPITs for the same point number. After programming all the points, perform a service walk test. The
D9412G/D7412G/D7212G Installation and Troubleshooting Quick Reference Guide (P/N: 43700) contains instructions for
performing a service walk test. If a point does not test, check the programming for a duplicated address.
Walk test does not show extra points:  If the point assignment switches on a POPIT or OctoPOPIT are set incorrectly, it may
create both missing and extra point conditions. If the same point number is assigned to two or more POPITs or
OctoPOPITs, none of the points with that number will test correctly. Refer to Section 8.1 Point (ZONEX) Bus D7212G
Terminals 27 to 28
 on page 37 for additional infomation on how to troubleshoot POPITs or extra point conditions.
8.4
D8128D OctoPOPIT Module
IMPORTANT
D8128, D8128A or D8128B modules are not compatible with the D7212G. Only use the D8128D OctoPOPIT
module. Using D8128, D8128A or D8128B modules may cause intermittent missing and restoral reports.
8.4.1
Description
The D8128D OctoPOPIT Module combines the functions of the D8125 POPEX module and the D8127/D9127 POPIT
modules to provide eight off-board points in a single module. You can wire both D8128D OctoPOPIT and D8125 POPEX
modules in parallel to the ZONEX Bus terminals on the same panel.
Review Section 5.0 Power Outputs on page 29 to be sure to provide enough power for the OctoPOPITs and other powered
devices that will be connected to the system.
8.4.2
Listing
The D8128D OctoPOPIT Module is UL Listed for Local or Police Connected Burglary Alarm, Central Station Burglary
Alarm, and Household Burglary Alarm applications. The D8128D is also suitable for fire supervisory applications, such as
indicating circuit supervision (using the D192C/D192G Bell Circuit Supervision Module), sprinkler supervision, and valve
tamper protection.
Do not connect fire alarm initiating devices directly to the D8128D.
You must use the D125B Dual Class B Powered Loop Interface Module or D129 Dual Class A Initiation Circuit Module for
fire initiation applications. Connect the initiating devices, smoke detectors for example, to the D125B powered loops or D129
Class A loops.
Connect the zone outputs on the D125B or D129 to the OctoPOPIT sensor loop inputs. The D125B or D129 and the
OctoPOPIT must be mounted in the enclosure with the panel or in a separate enclosure connected to the panel’s enclosure by
conduit no longer than 20 ft. (6 m).
8.4.3
Installing the OctoPOPIT
You can install the D8128D OctoPOPIT Module in the enclosure with the panel, or in a separate enclosure (D8103, D8108A,
or D8109) up to 200 ft. (61 m) from the panel, using standard four-conductor 22 AWG (0.8 mm) wire. If you mount the
OctoPOPIT in a separate enclosure, use shielded cable to avoid electro-magnetic interference. See EMI on Long Wire Runs in
the D9412G/D7412G/D7212G Installation and Troubleshooting Quick Reference Guide (P/N: 43700).
Tampered enclosures for UL Certificated systems: The D125B or D129 and the OctoPOPIT must be mounted in the enclosure
with the panel or in a separate enclosure connected to the panel’s enclosure by conduit not more than 20 ft. (6 m) in length.