Praesideo 3.5 | Installation and User Instructions | EN60849: 1998
en | 16
EN60849 - 4.2 Responsible person
EN60849 - 4.3 Priorities
EN60849 - 4.3.1 Classification of priorities
i
All messages shall be clear, short, unambiguous 
and as far as practicable, pre-planned.
Responsibility of the installer.
Where pre-recorded messages are used they shall 
be held in a non-volatile form, preferably in a solid-
state store, and be continuously monitored for 
availability.
First 128 MB of compact flash card is continuously 
monitored, which is equivalent to the first 25 minutes of 
audio.
The system design shall make it inherently 
impossible for an external source to corrupt or 
derange the store or its contents.
Compliant.
NOTE - On grounds of reliability, it is preferable not 
to use storage media depending on mechanical 
devices.
Storage medium is a compact flash card. Proper 
installation of the compact flash card is the 
responsibility of the installer.
j
The language(s) used shall be specified by the 
purchaser.
Responsibility of the installer.
k
The system shall be capable of being divided into 
emergency loudspeaker zones if required by the 
evacuation procedure. Such zones need not be the 
same as other zones, for example emergency 
detection zones or non-emergency loudspeaker 
zones.
Compliant, if properly installed. Responsibility of the 
installer.
l
In determining loudspeaker zones, the following 
criteria shall apply:
1
the intelligibility of messages broadcast in one 
zone shall not be reduced below the 
requirement of 5.1 by the broadcasting of 
messages in other zones or from more than one 
source.
Compliant, if properly installed. Responsibility of the 
installer.
2
no emergency detection zone shall contain 
more than one emergency loudspeaker zone. 
For non-emergency use, a loudspeaker zone 
may be subdivided.
Compliant, if properly installed. Responsibility of the 
installer.
m
A secondary power source shall be available 
(see 5.6).
Compliant, if properly installed. Responsibility of the 
installer.
Requirement
Compliance
Signature
The person or body, having control of the premises 
shall nominate a "responsible person", identified by 
name or job title, who shall be responsible for ensuring 
that the system is properly maintained and repaired so 
as to continue to operate as specified.
Responsibility of the person or body having control of 
the premises. Action to be taken care of by the installer.
Requirement
Compliance
Signature
It is necessary to decide upon an order of priority for 
the message distribution based upon:
a
Any automatic programmed response.
Compliant, if properly installed. Responsibility of the 
installer.
b
The perceived risk to occupants, which may require 
manual override of the programmed response.
Compliant, if properly installed. Responsibility of the 
installer.
Events shall be given a level of priority according to 
their urgency. The following primary levels are 
recommended but there may be advantages in adding 
further subgroups, depending on the operational 
strategies of the site:
Compliant, if properly installed. Responsibility of the 
installer.
a
Evacuate - potentially life-threatening situation 
needing immediate evacuation.
Compliant, if properly installed. Responsibility of the 
installer.
b
Alert - dangerous situation nearby requiring 
warning of pending evacuation.
Compliant, if properly installed. Responsibility of the 
installer.
c
Non-emergency - operational messages, e.g. 
system test, etc.
Compliant, if properly installed. Responsibility of the 
installer.
Requirement
Compliance
Signature