Bosch Appliances Home Security System 3.5 User Manual

Page of 498
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | 6 | Installation Accessories
en | 272
table 26.2: Kycon KPP-4P connector details
Pin
Signal
1
Ground
2
Power from external power supply to the 
PRS-FINxx (max. 48 V / 5 A)
3
Output power from the system bus 
(max. 48V / 2 A)
4
Not connected
Note
The pin numbers are also indicated on the inside 
of the connector.
For detailed connector assembly instructions, 
see appendix B
Warning
For safety reasons, you must use a current lim-
ited external power supply complying with the 
60065 standard for audio/video usage or equiv-
alent, with a maximum output current of 5A, or 
you must use an external fuse (5A max, slow) in 
the wiring to the Kycon KPP-4P connector. 
For application in emergency sound systems in 
Europe, the installer must use a power supply 
with EN54-4 certification.
Caution
For USA: only use a power supply of the type 
Mean Well PLN-30-24, PLN-30-36, 
PLN-30-48, PLN-60-24, PLN-60-36, 
PLN-60-48, PLN-100-24, PLN-100-36 or 
PLN-100-48.
For CANADA: only use a power supply of the 
type Mean Well PLN-30-24, PLN-30-36, 
PLN-60-24, PLN-60-36, PLN-100-24 or 
PLN-100-36.
Other types of power supply are not tested with
Praesideo and may cause harm.