POPIT modules monitor their sensor loops for three 
conditions: loop normal, loop open, and loop shorted. 
They send reports on these three conditions to the 
control panel. The control panel uses point 
programming to interpret the sensor loop information 
sent by the POPITs and to make the appropriate 
system response. 
P### BFSK/Relay 
Default: 
Refer to the program record sheet 
Selection:  0 to 9 
Use this option to: 
• 
• 
Determine the point number sent in BFSK format 
when this point is faulted. 
 
P### Area Assign 
Activate a relay when the point is faulted, even if 
the control panel is programmed for Modem IIIa
2
 
reporting format. Refer to 
Default: 
Selection: 
1 to 8 
 
The areas are numbered 1 to 8. Select the area 
number to which the point is assigned. 
P### Debounce 
Default: 
Selection
1 to 15 
1 .300 
sec 
2 .600 
sec 
3 .900 
sec 
4 1.2 
sec 
5 1.5 
sec 
6 1.8 
sec 
7 2.1 
sec 
8 2.4 
sec 
9 2.7 
sec 
10 3.0 
sec 
11 3.3 
sec 
12 3.6 
sec 
13 3.9 
sec 
14 4.2 
sec 
15 4.5 
sec 
The debounce count is the number of times the 
control panel scans a point before generating an 
alarm. Scan cycles are 300 ms. 
For appropriate settings consult the manufacturer’s 
instructions for the device connected to this point. 
 
 
Use an entry of two or higher. Interior 
Follower points need a Debounce value 
of at least three. 
 
 
 
Door points assigned to D9210B 
modules need a Debounce value of at 
least four. 
BFSK/Relays do not activate for Fire 
Supervisory or Non-Fire Supervisory 
points. 
 
 
Table 32: P### BFSK/Relay Codes/Relays 
 
Faults Relay 
D8129 on  
Zonex Bus 2  
for D9412GV2* 
D8129 on  
Zonex Bus 1  
for D7412GV2* 
BFSK Code 
73 
2 74  10 
75 
11 
4 76  12 
77 
13 
6 78  14 
79 
15 
8 80  16 
* Address setting = 1 (on), 2 (off), 3 (on), 4 (on) 
 
Local annunciation on the keypads, Local 
Printer reports, and the View Log show 
the actual point number (1 to 247), not 
 
the BFSK report code 
 
Do not assign a BFSK or relay to Invisible 
points. To avoid activating one of the 
associated relays, program this prompt  
 
as 0. 
On the D9412GV2, do not use Relays 73 
through 80 for Area or Panel-Wide Relay 
function when this prompt is enabled for 
the corresponding points. Refer to 
32
On the D7412GV2, do not use Relays 9 
through 16 for Area or Panel-Wide Relay 
function when this prompt is enabled for 
the corresponding points. Refer to 
32.