Bosch Appliances Video Game Controller D9412GV2 User Manual

Page of 158
D9412GV2/D7412GV2 | Program Entry Guide | 2.0  GV2MAIN 
EN | 21 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
 
 
 
Table 14: Diagnostic Reports (Continued) 
 
Report Selections 
Report 
Description 
R# Checksum Fail  Yes, No 
Checksum Fail 
Event 
R# Network Fail
4
Yes, No 
Failure of 
network 
R# Network Rest
4
Yes, No 
Restoral of 
network 
R# Network Cond
4
Yes, No 
Condition of 
network 
1  This event is included in the Expanded Test Report 
when an off-normal condition exists.. 
2  To meet UL 864 requirements for Central Station and 
Remote Station applications, enable AC FailBattery 
Missing
Low BatteryBattery Restoral, and AC 
Restoral
 reports. 
3  This event covers Comm Fail Route Group and Comm 
Fail Phone. If enabled, both events are sent; if disabled, 
neither event is sent 
4  This event is reserved for future use.
 
 
 
 
 
Enable Rt Comm Fail and Rt Comm 
Restore in only one route group. 
Relay Reports 
Selecting Yes enables sending a report when the 
event occurs. 
Table 15: Relay Reports 
 
Report Selections 
Report 
Description 
R# Sensor 
Reset 
Yes, No 
Sensor Reset 
Event 
R# Relay Set 
Yes, No 
Relay Set Event 
R# Relay 
Reset 
Yes, No 
Relay Reset Event 
 
 
When activating an on-board relay using 
remote automation software, the 
D9412GV2 and D7412GV2 Control 
 
Panels log and print the resulting event 
as: 
Relay 250 (Relay A) 
Relay 251 (Relay B) 
Relay 252 (Relay C) 
AutoFunc Reports 
The following prompts support customized routing of 
Auto Function Reports. Selecting Yes enables a 
report to be sent when the event occurs. 
Table 16: Auto-Function Reports 
 
Report Selections 
Report 
Description 
Yes, No 
R# Sked 
Sked Executed 
Executed 
Event 
Yes, No 
R# Sked 
Changed 
Sked Changed 
Event 
Yes, No 
R# Execute 
Fail to Execute 
Fail 
Event 
 
RPS Reports 
Selecting Yes enables sending a report when the 
RPS Passcode Event occurs. 
 
RPS Access Fail can indicate a wrong 
RPS passcode when communicating 
with the control panel or a valid RPS 
session terminated by a means other 
than a Good-bye or Reset-bye 
command. Remote Reset indicates a 
Reset-bye command issued from RPS; 
Bad Call to RPS indicates the control 
panel called RPS but was unable to 
connect.