D9412GV2/D7412GV2 | Program Entry Guide | 2.0  GV2MAIN 
EN | 53 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
 
 
 
 
CC# Assign Door 
When programmed to activate a relay, the 
[ENTER] key cannot be used for any 
Default: 
Blank 
other function. 
Relays used for this function must not be 
shared with any other point, sensor reset, 
control panel, or bell functions. Sharing 
can cause errors in relay operation. 
Selection:  1 to 8, Blank 
Blank No door controller is assigned for adding 
tokens or the CLOSE DOOR # appears on 
the keypad. 
 
1 to 8 The door controller assigned to this keypad 
is used to read new tokens when the Add 
User Mode is initiated.  
CC# Entr Cycl Dr 
Default: 
No 
If the assigned door remains open and this keypad 
has the CC# Close Door Warning Tone set to Yes
the CLOSE DOOR # message appears on this 
keypad. 
Selection:  Yes or No 
Yes 
The [ENTER] key is used to cycle the 
door programmed for CC Assign 
Door. 
•  If a door is not programmed for this 
No 
The [ENTER] key is not used to cycle 
the door. 
prompt and a door is not assigned to 
Enter Key Cycle Door: Program this prompt as Yes 
to start the door cycle sequence for the door number 
programmed in CC# Assign Door when a user 
enters a valid pass code and presses [ENTER]. This 
includes shunting the point assigned to the door. 
ACCESS GRANTED prints on the local printer and at 
the central station receiver, if programmed. 
 
 
•  The service pass code cannot be used 
for the CC# Entr Cycl Dr application. 
•  When programmed to activate a relay, 
the [ENTER] key cannot be used for 
any other function. 
•  Relays used for this function must not 
be shared with any other point, sensor 
reset, control panel, or bell functions. 
Sharing can cause errors in relay 
operation. 
•  The door does not cycle if Entr Key 
Rly is programmed. 
•  9210 NOT READY appears at this 
keypad when you press [ENTER] if the 
D9210B is not programmed with a D# 
Entry Area
 (in the RADAXS handler) 
or if CC Assign Door does not have a 
door number assigned. 
 
the area using the D# Entry Area in 
 
the RADAXS handler, 9210 NOT 
READY appears at this keypad when 
you attempt to add a user. The 
message indicates that the control 
panel cannot start the Add User Mode 
until a door is assigned to this keypad. 
•  Assigning a door to a keypad is not 
necessary for the user to control the 
door(s) using the Door Control 
function. Any door that is active can be 
controlled by a user who has the 
appropriate door control authority. The 
door control functions are available to 
a valid user at any keypad with access 
to the area where the door is 
assigned.  
 
During the Add User Mode, tokens or 
cards, door control requests, and 
RTE/REX do not function. Put the Door 
 
Mode into an unlocked state before 
adding users if there is heavy activity for 
this door.