D9412GV2/D7412GV2 | Program Entry Guide | 2.0  GV2MAIN 
EN | 74 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
 
L## Service Walk 
L## Default Text 
Default: 
Refer to the program record sheet 
Default: 
Refer to the program record sheet 
Selection:  Blank or E 
Selection:  Blank or E 
 
 
Function 
No. 
Function Name 
Alternate 
Keystroke 
Function Name 
Function 
No. 
Alternate 
Keystroke 
33 
Service Walk 
Test 
(Menu function 
only) 
34 Default 
Text 
[COMMAND][5][7] 
Temporarily show the armed state of the area using 
control panel default text, A# AREA # IS ON, A# NOT 
READY, A# AREA # IS OFF, and A# ACCOUNT IS 
ON. 
Start a Service Walk Test for all 24-hour Interior or 
Perimeter Controlled points in the control panel. 
Points are not included in this test if: 
• 
• 
• 
• 
• 
• 
• 
• 
• 
• 
Points are in an area that is already in a Walk 
Test Mode.  
L## Change Skeds 
Default: 
Refer to the program record sheet 
Points are assigned to an area that is not enabled 
A# Area On.  
Selection:  Blank or E 
 
Points are in an area that is Master or Perimeter 
armed. 
Function Name 
Function 
No. 
Alternate 
Keystroke 
35 Change 
Skeds 
[COMMAND][5][2] 
When a Service Walk Test is initiated, one person can 
test all the points in the control panel without 
assistance. The following features are provided with 
the Service Test Mode: 
Change skeds that can be edited. 
Editing of skeds can be restricted by 
Display indicates exactly how many points can be 
tested. 
programming S## Time Edit? to No
 
Battery and bell tests do not occur during this 
Walk Test. 
 
L## Invisible Walk Test 
The test ends when all points are tested or the 
test times out after 20 min of inactivity. 
Default: 
Refer to the program record sheet 
Selection:  Blank, or E 
Events print locally without alarm annunciation or 
reporting to the central station receiver. 
 
Function Name 
Function 
No. 
Alternate 
Keystroke 
D1255 Keypad displays a sequential count and 
the text for the point after each point is activated 
and restored.  
36 
Invisible Walk Test 
(Menu function only) 
Test all points that are programmed to be invisible 
and that are within the scope of the keypad without 
sending reports to the central station. Invisible points 
must be programmed P## Invisible Pt as Yes. This 
walk test mode can test 24-hour points and controlled 
points. 
The D1255 Keypad displays ALL PNTS TESTED. 
If enabled in Routing, Service Start and Service 
End are reported at the central station receiver for 
the beginning and end of the test. 
Point 128 and Point 248 appear as missing. This is 
normal. These points are used for supervising the 
Zonex 1 bus (Point 128) and Zonex 2 bus (Point 248). 
If the Zonex bus has a fault, these points indicate a 
short.  
Invisible Test? allows the user with this L## to start 
an invisible walk test for all 24-hour interior and 
posterior controlled points in the area to which this 
keypad is assigned. When an invisible test is started, 
one person can test invisible points without 
assistance.  
This function allows viewing of extra points. Extra 
points occur under two conditions: an extra point is 
wired electrically to the Zonex bus with a blank P### 
Point Index
, or two Zonex devices exist for the same 
Zonex address. 
The following features are provided with the Invisible 
Test Mode: 
• 
• 
The display indicates exactly how many invisible 
points are assigned to the area. 
Battery and bell tests do not occur during this 
walk test.