D9412GV2/D7412GV2 | Program Entry Guide | 4.0  RADXPNTS 
EN | 95 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
 
 
 
 
 
If you want this point to ring the bell 
because the message failed to reach the 
central station receiver, program P## 
Audible After 2 Failures
 as Yes
P## Ring Til Rst 
Default: 
No 
Selection: 
Yes or No 
Yes 
The relay programmed to provide 
fire alarm output for this point cannot 
be de-activated until the point 
restores to normal. 
No 
The relay programmed to provide 
fire alarm output for this point can be 
de-activated before the point 
restores to normal. 
Use this option to determine if the bell continues to 
ring until the Fire Bell time expires. The point returns 
to a normal condition when the user acknowledges 
the alarm to silence the bell. 
 
 
If the point restores and the fire alarm is 
not silenced from the keypad, the fire 
alarm output continues until Fire Bell time 
expires. If the point does not restore, the 
fire alarm output continues even after bell 
time expires. 
 
 
 
Use this option for fire applications to 
meet the requirement that audible alarms 
cannot be silenced until the fault condition 
clears or the Fire Bell time expires. 
 
P## Audible After 2 Failures 
Default: 
No 
Selection:  Yes or No 
Yes 
A# Burg Alarm relay activates after 
two failed attempts. 
No 
P## Silent points do not cause the 
A# Burg Alarm relay to activate even 
if the report does not get to the 
central station receiver. 
When set to Yes, if the report fails to reach the 
central station after two attempts, a silent alarm rings 
the A## Burg Alarm bell. A silent alarm is generated 
when a point with P## Silent set to Yes is faulted 
while armed.  
When a point programmed for P## Silent 
Bell
 is faulted, the timer for the A# Burg 
Time
 starts, even though the bell is not 
 
yet ringing. As much as 3 min can elapse 
before the second attempt fails. Ensure 
that A# Burg Time is programmed to 
provide the amount of bell time you need, 
minus the additional 3 min that might 
elapse before the bell actually begins to 
ring. 
P## Invisible Pt 
Default: 
Refer to the program record sheet 
Selection: 
Yes or No 
Keypads do not display alarm 
activity from this point. 
Yes 
No 
Activity from this point is visible at 
the keypads. 
 
To meet UL 864 requirements, set this 
parameter to No
 
Use this option to determine whether the point 
appears in the keypad display upon an alarm 
condition. For LED keypads, the LED does not 
illuminate upon an alarm condition. Point text 
appears and annunciation is made for Invisible points 
programmed for a trouble condition in point response. 
 
To prevent the keypad alarm tone and the 
A# Burg Alarm bell from sounding, 
program P## Silent Bell as Yes
 
 
If a user enters a valid pass code while a 
bell is ringing for an invisible alarm, the 
keypad shows ALARM SILENCED.