INSTALLER/CONFIGURATION MENU 
1 & 2)
Keypad Lockout – This menu selection will display 
Lk” and “OFF” (default, keypad not locked out). The 
 and 
 are used to toggle the selection between 
OFF and “L” (keypad locked out). When the keypad 
lockout selection is enabled 
“L”, and the MENU button 
is pressed again, the display will indicate the number 
“0” (default, still disabled) in the time digits. The 
 
and 
 are used to set the combination number from 
0 
to 
999. If a combination of 0 is selected and the MENU 
button is pressed, the menu will be exited and keypad 
will not be locked. If 
1 to 999 is selected and the MENU 
button is pressed, the combination is stored into memory 
and the menu is exited. The “
Lk” will display designating 
keypad locked with a valid combination. The SYSTEM 
button will operate for 10 seconds after the menu mode 
is exited to allow the user to change the mode from 
OFF” to the desired SYSTEM mode.
 
While the keypad is locked out, a press of MENU will en-
ter the configuration menu. The first menu item displayed 
is the combination code “
0”. The 
 or 
 keys are 
used to set the combination unlock number from 
to 
999. If the unlock number matches exactly with the com-
bination lock number stored in memory when the MENU 
button is pressed, the keypad is unlocked and the 
“Loc” 
is removed. If the unlock number does not match when 
the MENU button is pressed, the combination returns to 
“0” for another attempt to set the unlock code. To exit the 
menu without unlocking the keypad, press RUN SCHED.
 
To reset the combination code and unlock the keypad if 
the code is forgotten, see troubleshooting section.
3) 
Select Reversing Valve Output (SS/HP switch must be set 
at HP, omitted if SS/HP switch is SS Position) – The O/B 
option is factory set at "O" position. This will accommodate 
the majority of heat pump applications, which require the 
changeover relay to be energized in COOL. If the thermo-
stat you are replacing or the heat pump being installed 
with this thermostat requires a "B" terminal, to energize the 
changeover relay in HEAT, the O/B option should be set at 
"B" position.
To enter the Configuration Menu, SYSTEM must be set to 
HEATCOOLEm or AUTO. Press the Menu button for at least 5 
seconds. The display will show item #1 in the table below. Press Menu button to advance to the next menu item. Press 
 or 
 to change an item option. Shaded items are not available on 1F86. 
INSTALLER/CONFIGURATION MENU        
Menu 
Screen 
Number
SS HP
Displayed
(Factory Default)
Press 
 or 
 to
select from listed options
Comments
01
(OFF) Lk
L
Selects Keypad Lockout. 
(Not available on earlier models)
02
(000) Lk
001  to 999
Selects Keypad lockout combination number 
03
(Cool O) On
Heat b On
Reversing Valve Output (SS/HP switch must be in 
the Heat Pump HP position)
04
(2) P
P 3, P 0
Selectable Programs Per Week
(For programmable thermostat only)
05
(OFF)
Cool Savings CS
Cool Savings CS On
Select Cool Savings On of OFF
06
(3) CS
6, 5, 4, 3, 2, 1
Selects Cool Savings value 1 (low) to 6 (high)
07
(On) E
E OFF
Selects Energy Management Recovery (EMR)
On or OFF 
(For programmable thermostat only)
08
(ME) 
CR Heat
SL, FA
Adjustable Anticipation (Heat) (only when SS/HP 
switch is at the SS position)
09
(FA)
CR Cool
SL
Adjustable Anticipation (Cool) (only when SS/HP 
switch is at the SS position) 
10
(FA) 
CR Heat Pump
SL
Adjustable Anticipation (Heat Pump) 
(only when SS/HP switch is at the HP position)
11
(OFF) CL
CL On
Compressor Lockout Time
12
Auto-Heat
Cool-Off
Heat-Cool-Off, Heat-Off 
with Fan icon,
Heat-Off without Fan icon, 
Cool-Off, Auto-Off
System Mode Configuration with Automatic 
Changeover
13
(On) dL
OFF
Selects Display Light On or OFF
14
0 HI
1 HI, 2 HI, 3 HI, 4 HI,
1 LO, 2 LO, 3 LO, 4 LO
Adjustable Ambient Temperature Display
15
°
F
°
C
Selects Fahrenheit/Celsius Temperature Display
16
L (90) Heat
L 62 to L 89
Selects Limited HEAT Range
17
L (45) Cool
L 46 to L 82
Selects Limited COOL Range
18
(OFF) Change Filter
Change Filter On
Selects Filter Change-out Indicator
19
(200 h) Change 
Filter
25 h to 1975 h in
25-hour increment
When on, selects time in 25 hour increments 
25-hour increment