White Rodgers 16E09-101 Electronic Temperature Control Installation Instruction

Page of 16
4
USER MENU OPERATION SETTINGS:
The control has user Menu settings that will determine how 
the control operates. The unit is shipped with factory de-
fault settings. The user must change any of the settings as 
required for the application. To reset all settings to factory 
defaults, press and hold all 3 buttons simultaneously (
, and   buttons) for approximately 5 seconds.  
To view Menu items, press and hold 
 for 5 seconds. 
The unit will display the first Menu item on the left side of the 
display. The right side of the display indicates the Menu item 
settings. To change the setting, momentarily press the   or 
 key.
A momentary press of the 
 key advances the display to 
the next Menu item, and continues, till the last menu item is 
displayed. Pressing the key one more time with the 
last menu 
item, (aL) displayed returns the control to the operating mode.
USER MENU 
Each press of 
 results in forward movement to the next 
Menu item. If you need to change an item “passed”, you 
must repeatedly press 
, return to the operating mode, 
then press and hold 
 for 5 seconds to re-enter the Menu 
mode. Then repeatedly, momentarily press 
 until the 
desired Menu item is again displayed.
To store any changes made to any Menu items, the Menu 
must be exited by pressing 
 when the last item is 
displayed. If no buttons are pressed for ten minutes while in 
the menu, the control will return to operating mode and any 
changes that were made will be lost.
The following table shows the menu items, default settings 
and optional settings.
NOTE: The Heat/ Cool switch (SW1) MUST be in the proper 
position BEFORE setting options.
Menu
Item
Description
Factory
Default
Options
Press   or 
to select
Comments
CF
Temperature Scale
F
C or F
Selects temperature display in Fahrenheit or Celsius
dFF
Differential
5
1 to 30
Selects the range between Cut In and Cut Out.
SP
Set Point Mode
Cool
Heat
Cl
CO
CO or CI
CI or CO
Selects how the set point temperature will operate the 
load terminal. CI indicates the setpoint temperature 
will be the Cut In temperature. CO indicates the 
temperature will be the Cut Out temperature. See 
Operation section.
SOF
Sensor Operation Failure
Cool
Heat
1
0
0 or 1
None
Cooling - Selects the operation of the Control Load 
relay in the event of a sensor failure in Cool mode. 1 
(default) will cause the load contacts of the relay to 
close and remain closed if the sensor either opens or 
shorts. 0 causes the load contacts of the relay to open 
and remain open.
Heating has no optional selection. Sensor failure
in Heating will result in the relay contacts opening.
dL
Display Light
Off
On or Off
Selects the LCD display light Off or On. With this 
selected Off, the display light will illuminate any time a 
keypad button is pressed to provide better viewing in 
low lighting conditions, and go off after 10 seconds. If 
On is selected, the display light will be On continuously.
ASd
Anti Short-Cycle Delay
Cool
1
Heat
0
0 to 12
Selects the minimum time (in minutes) that the load 
contacts will remain open after a cycle before closing 
again. This will prevent the compressor or other load 
from being damaged by cycling too soon. A blinking 
Snowflake or Flame icon indicates that the control has 
a demand to energize the load, but is waiting for the 
delay time to elapse. A setting of 0 indicates no time 
and the feature is disabled. SW1 must be set to the 
proper position before checking this setting.
LP
Lock Front Panel Keypad
Off
On or Off
When selected Off, the keypad can be used as normal. 
When selected On, prevents unauthorized access to 
the control settings by locking out all keys. To unlock 
the control when it is locked, press and hold the Menu 
key for 5 seconds.
OFS
Ambient Temperature
Offset
0
-4, -3, -2, -1, 0,
1, 2, 3, 4
This control is calibrated at the factory, but the “sensed" 
temperature may read different because of mount-
ing/installation, or other factors. This item allows the 
displayed temperature to be shifted the number of 
degrees set to compensate for this difference