An 8000 Series node comprises single or redundant 
Ethernet Bus Inter-face Modules, up to 64 I/O modules, 
field terminals, and associated power supplies. 
A schematic node architecture is shown below. In-
formation from the I/O modules is transferred to and 
from the communication module (EBIM) via the Rail-
bus. The Railbus is a fast, serial data bus with parallel 
module addressing and extends over the full length of 
the node. The parallel address architecture means that 
each I/O module position has a unique address which 
eliminates the need to ‘train’ modules during installa-
tion. 
Power for the node is provided by integrated power 
supply modules; these convert the locally available 
power source into a regulated internal supply rail. This 
rail energizes the EBIM and all Railbus communication 
between the EBIM and I/O modules. 
For some I/O module types—such as those with 
low-power and intrinsically safe field circuits—it also 
provides power for the field wiring. Where additional 
power is required for field devices (such as high cur-
rent AC circuits), power can be provided by means 
of cabled connections from each module to external 
relays. This Bussed Field Power facility reduces instal-
lation time by removing the need to make daisy chain 
wiring connections at the field terminals of each I/O 
module.
 
Node Operation
A typical request for data from the field might happen 
as follows: 
The D/3® PAS requires the temperature from a par-
ticular thermocouple input at a particular node and 
transmits a signal on the I/O LAN. There are several 
Series 8000 nodes on the I/O LAN, but the EBIM at the 
chosen node recognizes its own node address, and 
acknowledges the request. 
At each node, the input modules constantly monitor, 
linearize and digitize their respective field signals, 
and make them available to scanning on the node’s 
internal bus (Railbus). 
The EBIM continually scans the I/O modules via the 
Railbus, and builds up a map of the values of the input 
variables, ready for the PCM to read. These are con-
verted into the LAN protocol and placed on the LAN 
by the EBIM, together with acknowledgement signals. 
The D/3 then interprets the signal and reconstructs 
the temperature reading.
8000 Series I/O
®
Product Catalog
8000 Series I/O