NovaTech 8000 Series I/O Components
Modules
I/O modules transfer signals to and from field instru-
ments. Input modules receive signals from transmit-
ters and sensors and convert them into a digital form 
for presentation to the EBIM. Output modules receive 
commands from the EBIM and transfer them to actua-
tors. A wide range of modules is available, including 
types for low-level instrumentation, AC circuits, and 
intrinsically safe signals. I/O modules typically have 4, 
8, or 16 field channels. 
Carriers
Carriers allow the 8000 Series I/O to mount onto a flat 
panel or T- or G-section DIN rail. They support and in-
terconnect the EBIM, power supplies, I/O modules and 
field terminals, and carry the address, data and power 
lines of the internal Railbus. They provide termination 
points for the LAN and field wiring cable screens and 
can also distribute bussed field power to the I/O mod-
ules. I/O module carriers support eight I/O modules. 
Field Terminals
Field terminals provide the interface between the 
I/O modules and the field wiring. They include fusing 
and loop disconnect as options. A mechanical keying 
system prevents an I/O module from being connected 
to the wrong type of field terminal. Field terminals 
mount onto the module carrier, one to each I/O 
module. They are clamped firmly by the I/O module 
to form an electrical and mechanical assembly of high 
integrity. They may be replaced in service without 
removing carriers or disturbing the operation of other 
modules. 
Power Supplies
8000 Series I/O power supplies accept locally available 
unregulated power and provide a regulated supply 
for the EBIM and I/O modules. Supply redundancy is 
supported. The system power supply at an 8000 Series 
node converts the local DC supply to power the node, 
and can also provide field power for I/O modules with 
low-level field circuits. Where heavy-current or AC 
mains circuits are handled by the I/O modules, the 
8000 Series method for distributing field power avoids 
complex wiring at the field terminal and minimizes the 
backplane/carrier wiring. 