NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
C
himney
 r
equirements
The  Performer™  C/A210  inserts  are  approved  for  use  in 
masonry fireplaces built to UBC Chapter 37 or equivalent 
with a minimum 22” (559mm) opening at the front of the 
fireplace.
These heaters are designed to be installed into an existing 
masonry fireplace (built to UBC 37 or  ULC S628 standards) 
or factory-built, solid-fuel and wood-burning fireplaces (listed 
to UL 127 or ULC S610) only. 
Do not remove brick or mortar from masonry fireplace to 
accommodate insert. Do not remove brick or mortar from 
masonry fireplace to accommodate insert.  Approved with or 
without positive flue connection.  Approved with minimum 
6” (152mm) diameter stainless steel listed reline system.  
Ask your dealer for recommended chimney size. Country 
Collection inserts are tested to  UL 1482 / ULC S628-93 and 
listed by OMNI-Test Laboratories, Inc.; Beaverton, OR.
Remove and clean behind unit frequently, as creosote build 
up may occur rapidly.
i
nstallation
 P
roCeDures
- m
asonry
 C
himney
 
Note: Although not required, a full-length stainless steel liner 
is recommended for optimum safety and performance.  See 
your Lennox Hearth Products dealer for details.
Note:  When installing your stove with a positive flue connec-
tion, be sure to leave the insulation off the surround panels 
(flanges) and leave  a 1/4” (6mm) airspace insulation off the 
surround panels and the facing of your fireplace.
1. READ ENTIRE INSTALLATION INSTRUCTIONS.
2. Check all REQUIRED CLEARANCES as specified in the 
previous section (page 7) of this installation instruction 
booklet.
3. Wear gloves during installation in case of sharp edges on 
the stove and it’s parts
4. Determine the depth of the fireplace lintel.  The lintel is 
the masonry area over the fireplace opening, and is sup-
ported by a noncombustible plate, usually of steel.  The 
depth may vary from a single brick width (4”/102mm) 
to that of several brick.  If any portion of the flue collar 
opening on top of the insert (as shown in the diagram 
below) will project under the lintel area, a deflector plate 
must be mechanically attached to the fireplace insert to 
divert heat and gases away from the lintel.  
  Consult  your  dealer  for  the  correct  attachment  piece.  
Compare lintel depth to the distance from the flue collar 
opening to the fireplace to determine if this caution per-
tains to your installation.  If there is sufficient clearance, 
a flue offset may also be used.  Consult your dealer. 
5. Open or remove the existing fireplace damper.  Make sure 
the damper cannot fall closed.
6. Install the two 1/2” x 3” (13mm x 76mm) leveling bolts 
-heads up- a few turns in the leveling nuts on each side 
of the outer chamber of the insert at the lower rear cor-
ners.
7. Position the insert in the center of the fireplace opening 
and push it back until the surround brackets are approxi-
mately 2” (51mm) away from the fireplace front.
8. Install the side surround panels and push the insert up 
snug against the fireplace face.  Then with the location 
selected remove the surround panels and level the stove 
with the leveling bolts using a 3/4” (19mm) socket, exten-
sions (to reach the bolt head), and a ratchet.
9. Glue the insulation around the outer edge of both the top 
and side surround panels.
10.  Install the surround panels loosely, align and tighten.  
Check for a tight fit against the fireplace.
11.Install the brick and baffle as per instructions on page 
6.
POSITIVE FLUE CONNECTION: See your authorized Len-
nox Hearth Products dealer for necessary accessories and 
installation instructions.
Positive flue connectors required for installation in Canada 
are  available  from  your  Lennox  Hearth  Products  dealer. 
Please use the part number indicated below.
71161 - 6" Positive Flue Connector Ring Kit
Lintel
Flue Outlet
Not to Scale
Brick Face
Insert Surround
 
Smoke 
Deflector
Mechanically
Attached to
Insert
Figure 7