APC Condenser 2 EC Fan ACCD75208 User Manual

Product codes
ACCD75208
Page of 50
17
InRow RP Technical Data Manual
Performance Specifications
Chilled Water Performance Specifications 5.5°C (42°F) EWT
Temperature dry bulb 
(DB), wet bulb (WB)
°C (°F)
CW Delta T
°C (°F)
Total Net 
Capacity
kW (BTU/hr)
Sensible Net 
Capacity
kW (BTU/hr)
Sensible Heat 
Ratio
SHR
 CW Flow 
Rate
l/s (GPM)
Total CW 
Pressure Drop
kPa (ft H2O)*
26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB)
6.6 (12)
44.3 (151,000)
40.7 (139,000)
0.92
1.6 (25.9)
66 (21.95)
7.7 (14)
40.8 (139,000)
37.9 (129,000)
0.93
1.3 (20.6)
42 (14.1)
8.8 (16)
37.8 (129,000)
35.2 (120,000)
0.93
1.1 (16.8)
29 (9.5)
10 (18)
34.6 (118,000)
32.5 (111,000)
0.94
0.9 (13.8)
19 (6.5)
11.1 (20)
31.8 (109,000)
29.9 (102,000)
0.94
0.7 (11.5)
14 (4.6)
29.4°C DB, 18.1°C WB (85°F DB, 64.5°F WB)
6.6 (12)
50.8 (174,000)
47.8 (163,000)
0.94
1.9 (29.5)
84 (28.4)
7.7 (14)
47.7 (163,000)
44.8 (153,000)
0.94
1.5 (23.9)
56 (18.7)
8.8 (16)
44.1 (151,000)
41.9 (143,000)
0.95
1.2 (19.4)
38 (12.5)
10 (18)
41.2 (141,000)
39.1 (134,000)
0.95
1.0 (16.2)
26 (8.8)
11.1 (20)
37.8 (129,000)
36.3 (124,000)
0.96
0.8 (13.5)
19 (6.2)
32.2°C DB, 18.9°C WB (90°F DB, 66.1°F WB)
7.7 (14)
54.5 (186,000)
52.3 (179,000)
0.96
1.7 (27.1)
71 (23.8)
8.8 (16)
51.4 (175,000)
49.3 (168,000)
0.96
1.4 (22.4)
49 (16.6)
10 (18)
47.8 (163,000)
46.3 (158,000)
0.97
1.2 (18.6)
35 (11.6)
11.1 (20)
44.8 (153,000)
43.4 (148,000)
0.97
1.0 (15.7)
25 (8.32)
35.0°C DB, 19.8°C WB (95°F DB, 67.7°F WB)
7.7 (14)
62.0 (212,000)
60.2 (205,000)
0.97
1.9 (30.6)
90 (30.3)
8.8 (16)
58.8 (201,000)
57.0 (195,000)
0.97
1.6 (25.4)
63 (21.3)
10 (18)
55.6 (190,000)
53.9 (184,000)
0.97
1.4 (21.4)
45 (15.2)
11.1 (20)
52.4 (179,000)
50.9 (174,000)
0.97
1.2 (18.3)
33 (11.1)
37.8°C DB, 20.7°C WB (100°F DB, 69.2°F WB)
8.8 (16)
66.4 (227,000)
65.0 (222,000)
0.98
1.8 (28.6)
79 (26.6)
10 (18)
63.1 (215,000)
61.8 (211,000)
0.98
1.5 (24.2)
57 (19.2)
11.1 (20)
59.8 (204,000)
58.7 (200,000)
0.98
1.3 (20.7)
42 (14.3)
40.6°C DB, 21.6°C WB (105°F DB, 70.8°F WB)
10 (18)
71.4 (244,000)
70.0 (239,000)
0.98
1.7 (27.3)
72 (24.3)
11.1 (20)
68.1 (233,000)
66.7 (228,000)
0.98
1.5 (23.4)
54 (18.02)
Note: All values are accurate to +/- 5% and based on full speed with standard filters.
Note: Reduce airflow and cooling capacity specifications by 7% for cooling units run at low input voltage (380 V).
Note: Any CW flow rate of 0.19 l/s - 0.32 l/s (3.0 GPM - 5.0 GPM) may cause an increased error in flow rate and power calculation. A 
fluid flow fault may result. Any flow rate under 0.19 l/s (3.0 GPM) may also display as 0 in the flow rate and power calculation.
Note: For sustained operation, a maximimum flow rate of 2.2 l/s (34 GPM) is recommended. This may be exceeded by 25% for peak 
conditions.
* To convert feet of water to PSIG, use the following formula: ft H2O ÷ 2.307 = PSIG.