InRow RP Technical Data Manual
Chilled Water Performance Specifications 8.9°C (48°F) EWT
 (
Temperature dry bulb 
(DB), wet bulb (WB)
°C (°F)
CW Delta T
°C (°F)
Total Net 
Capacity
kW (BTU/hr)
Sensible Net 
Capacity
kW (BTU/hr)
Sensible Heat 
Ratio
SHR
 CW Flow Rate
l/s (GPM)
Total CW Pressure 
Drop
kPa (ft H2O)*
26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB)
5.5 (10)
35.7 (122,000)
34.6 (118,000)
0.97
1.6 (25.5)
63 (21.3)
6.6 (12)
32.9 (112,000)
31.9 (109,000)
0.97
1.2 (19.7)
39 (12.9)
7.7 (14)
30.3 (103,000)
29.4 (100,000)
0.97
1.0 (15.7)
25 (8.3)
8.8 (16)
27.7 (95,000)
26.9 (92,000)
0.97
0.8 (12.7)
17 (5.5)
10 (18)
25.3 (86,000)
24.5 (84,000)
0.97
0.7 (10.4)
11 (3.9)
11.1 (20)
22.7 (78,000)
22.3 (76,000)
0.98
0.5 (8.5)
8 (2.5)
29.4°C DB, 18.1°C WB (85°F DB, 64.5°F WB)
5.5 (10)
42.3 (145,000)
41.5 (142,000)
0.98
1.9 (29.9)
86 (28.9)
6.6 (12)
39.4 (134,000)
38.6 (132,000)
0.98
1.5 (23.3)
53 (17.8)
7.7 (14)
36.5 (125,000)
35.8 (122,000)
0.98
1.2 (18.6)
35 (11.6)
8.8 (16)
33.7 (115,000)
33.1 (113,000)
0.98
1.0 (15.1)
23 (7.9)
10 (18)
31.1 (106,000)
30.4 (104,000)
0.98
0.8 (12.5)
16 (5.3)
11.1 (20)
28.5 (97,000)
27.9 (95,000)
0.98
0.7 (10.4)
12 (3.9)
32.2°C DB, 18.9°C WB (90°F DB, 66.1°F WB)
6.6 (12)
47.0 (161,000)
46.1 (157,000)
0.98
1.7 (27.5)
73 (24.5)
7.7 (14)
43.9 (150,000)
43.0 (147,000)
0.98
1.4 (22.1)
48 (16.2)
8.8 (16)
40.9 (140,000)
40.1 (137,000)
0.98
1.1 (18.1)
33 (10.9)
10 (18)
37.6 (128,000)
37.2 (127,000)
0.99
0.9 (14.9)
23 (7.6)
11.1 (20)
34.8 (119,000)
34.4 (118,000)
0.99
0.8 (12.5)
16 (5.3)
35.0°C DB, 19.8°C WB (95°F DB, 67.7°F WB)
7.7 (14)
51.4 (176,000)
50.9 (174,000)
0.99
1.6 (25.6)
64 (21.5)
8.8 (16)
48.2 (165,000)
47.7 (163,000)
0.99
1.3 (21.1)
44 (14.8)
10 (18)
45.0 (154,000)
44.6 (152,000)
0.99
1.1 (17.6)
31 (10.4)
11.1 (20)
42.0 (143,000)
41.6 (142,000)
0.99
0.9 (14.8)
22 (7.6)
37.8°C DB, 20.7°C WB (100°F DB, 69.2°F WB)
7.7 (14)
60.0 (205,000)
59.4 (203,000)
0.99
1.9 (29.7)
85 (28.6)
8.8 (16)
56.0 (191,000)
56.0 (191,000
1.00
1.5 (24.3)
58 (19.4)
10 (18)
52.6 (180,000)
52.6 (180,000
1.00
1.3 (20.4)
41 (13.9)
11.1 (20)
49.4 (169,000)
49.4 (169,000)
1.00
1.1 (17.3)
30 (9.9)
40.6°C DB, 21.6°C WB (105°F DB, 70.8°F WB)
7.7 (14)
68.6 (234,000)
68.6 (234,000)
1.00
2.1 (33.7)
109 (36.5)
8.8 (16)
64.9 (222,000)
64.9 (222,000)
1.00
1.8 (28.0)
76 (25.4)
10 (18)
61.3 (209,000)
61.3 (209,000)
1.00
1.5 (23.5)
54 (18.2)
Note: All values are accurate to +/- 5% and based on full speed with standard filters.
Note: Reduce airflow and cooling capacity specifications by 7% for cooling units run at low input voltage (380 V).
Note: Any CW flow rate of 0.19 l/s - 0.32 l/s (3.0 GPM - 5.0 GPM) may cause an increased error in flow rate and power calculation. A 
fluid flow fault may result. Any flow rate under 0.19 l/s (3.0 GPM) may also display as 0 in the flow rate and power calculation.
Note: For sustained operation, a maximimum flow rate of 2.2 l/s (34 GPM) is recommended. This may be exceeded by 25% for peak 
conditions.
* To convert feet of water to PSIG, use the following formula: ft H2O ÷ 2.307 = PSIG.