20
Chilled Water Performance Specifications 10°C (50°F) EWT
Temperature dry 
bulb (DB), wet bulb 
(WB)
°C (°F)
CW Delta T
°C (°F)
Total Net 
Capacity
kW (BTU/hr)
Sensible Net 
Capacity
kW (BTU/hr)
Sensible Heat 
Ratio
SHR
 CW Flow Rate
l/s (GPM)
Total CW 
Pressure Drop
kPa (ft H2O)*
26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB)
5.5 (10)
32.6 (111,000)
31.8 (109,000)
0.98
1.5 (23.5)
54 (18.02)
6.6 (12)
29.9 (102,000)
29.2 (100,000)
0.98
1.1 (18.1)
33 (11.1)
7.7 (14)
27.4 (93,000)
26.7 (91,000)
0.98
0.9 (14.3)
21 (6.9)
8.8 (16)
24.9 (85,000)
24.3 (83,000)
0.98
0.7 (11.5)
14 (4.6)
10 (18)
22.6 (77,000)
22.0 (75,000)
0.98
0.6 (9.4)
10 (3.2)
11.1 (20)
20.4 (70,000)
19.9 (68,000)
0.98
0.5 (7.7)
7 (2.3)
29.4°C DB, 18.1°C WB (85°F DB, 64.5°F WB)
5.5 (10)
39.6 (135,000)
38.6 (132,000)
0.98
1.8 (28.0)
76 (25.6)
6.6 (12)
36.6 (125,000)
35.7 (122,000)
0.98
1.4 (21.8)
47 (15.7)
7.7 (14)
33.8 (115,000)
32.9 (112,000)
0.98
1.1 (17.3)
30 (10.2)
8.8 (16)
31.1 (106,000)
30.3 (103,000)
0.98
0.9 (14.0)
20 (6.7)
10 (18)
28.5 (97,000)
27.7 (95,000)
0.98
0.7 (11.5)
14 (4.6)
11.1 (20)
26.0 (89,000)
25.3 (86,000)
0.98
0.6 (9.5)
10 (3.2)
32.2°C DB, 18.9°C WB (90°F DB, 66.1°F WB)
6.6 (12)
43.6 (149,000)
43.2 (147,000)
0.99
1.6 (25.6)
64 (21.5)
7.7 (14)
40.5 (138,000)
40.1 (137,000)
0.99
1.3 (20.5)
42 (13.9)
8.8 (16)
37.6 (128,000)
37.2 (127,000)
0.99
1.1 (16.7)
28 (9.5)
10 (18)
34.7 (119,000)
34.4 (117,000)
0.99
0.9 (13.8)
20 (6.5)
11.1 (20)
32.0 (109,000)
31.7 (108,000)
0.99
0.7 (11.5)
14 (4.6)
35.0°C DB, 19.8°C WB (95°F DB, 67.7°F WB)
6.6 (12)
51.9 (177,000)
51.4 (175,000)
0.99
1.9 (30.1)
88 (29.3)
7.7 (14)
48.5 (166,000)
48.0 (164,000)
0.99
1.5 (24.2)
58 (19.4)
8.8 (16)
45.3 (155,000)
44.8 (153,000)
0.99
1.3 (19.9)
39 (13.2)
10 (18)
42.1 (144,000)
41.7 (142,000)
0.99
1.0 (16.5)
28 (9.2)
11.1 (20)
38.7 (132,000)
38.7 (132,000)
1.00
0.9 (13.7)
19 (6.5)
37.8°C DB, 20.7°C WB (100°F DB, 69.2°F WB)
7.7 (14)
56.7 (194,000)
56.7 (194,000)
1.00
1.8 (28.1)
77 (25.6)
8.8 (16)
53.2 (182,000)
53.2 (182,000)
1.00
1.5 (23.1)
53 (17.6)
10 (18)
49.8 (170,000)
49.8 (170,000)
1.00
1.2 (19.3)
37 (12.5)
40.6°C DB, 21.6°C WB (105°F DB, 70.8°F WB)
8.8 (16)
62.3 (213,000)
62.3 (213,000)
1.00
1.7 (26.9)
70 (23.6)
Note: All values are accurate to +/- 5% and based on full speed with standard filters.
Note: Reduce airflow and cooling capacity specifications by 7% for cooling units run at low input voltage (380 V).
Note: Any CW flow rate of 0.19 l/s - 0.32 l/s (3.0 GPM - 5.0 GPM) may cause an increased error in flow rate and power calculation. A 
fluid flow fault may result. Any flow rate under 0.19 l/s (3.0 GPM) may also display as 0 in the flow rate and power calculation.
Note: For sustained operation, a maximimum flow rate of 2.2 l/s (34 GPM) is recommended. This may be exceeded by 25% for peak 
conditions.
* To convert feet of water to PSIG, use the following formula: ft H2O ÷ 2.307 = PSIG.