D9412GV3/D7412GV3 | Program Entry Guide | 2.0  Panel and Area Wide Parameters 
EN | 29 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
2.4 Power 
Supervision 
AC Fail Time 
Default: 
1:00 
Selection:  0:01 to 90:00 
Program the amount of time that AC power must be 
off before the control panel responds to the AC 
failure. The response to restoral of AC power is 
delayed for the same amount of time. The control 
panel always monitors AC. The response to this 
prompt is the actuation of the relay programmed in 
the Panel-Wide Relays prompt AC Failure (refer to 
Section 2.12.2 Panel-Wide Relays on page 81) and 
the AC Fail report enabled by the AC Fail/Restoral 
Report
 prompt. Local annunciation of an AC failure is 
controlled by the AC Fail Display prompt. 
 
 
UL 864 requirements, Section 50.2.1.b 
states: “A trouble signal shall be 
transmitted for remote station, central 
station, and proprietary-type protected 
premises units after a delay of between 
60 and 180 min. 
Exception: Products are not prohibited 
from providing capability of selecting 
that the primary power failure trouble 
signal transmission be delayed other 
time periods, including no delay, 
provided the 60 – 180 min delay is also 
included.” 
To meet UL 864 requirements, program 
AC Fail Time with 1:00. Always check 
with the Authority Having Jurisdiction for 
local requirements. 
 
Resend AC Fail 
Default: 
No Response 
Selection: 
No Response, 6 hrs, 12 Hrs 
No 
Response 
Only send the AC Fail report upon 
failure. 
6 hr 
Send AC Fail report upon failure and 
every 6 hours after this while the 
failure persists. 
12 hr 
Send AC Fail report upon failure and 
every 12 hours after this while the 
failure persists. 
 
This prompt controls the repeated transmission of the 
AC Failure report to the central station while the fault 
persists. AC Fail/Restoral Report must be set to 
Yes, and AC Tag Along must be set to No for this 
feature to work. 
 
For the following items to be true, AC 
Fail/Restoral Report
 must be 
programmed as Yes and AC Tag Along 
must be programmed as No
 
 
To eliminate AC Reporting, AC Tag 
Along
 and AC Fail/Restoral Report 
must be programmed as No
 
AC Fail Display 
Default: 
60 sec 
Selection: 
10 to 300 sec (in 5-sec 
increments) 
 
Program the length of time the AC power must be off 
before the message SERVC AC FAIL shows on the 
keypads. The response to restoral of AC power is 
delayed for the same amount of time. 
 
AC Fail/Restoral Report 
Default: 
No 
Selection: 
Yes or No 
Yes 
Send AC Fail and AC Restoral 
Reports. 
No 
Does not send AC Fail and AC 
Restoral Reports. 
AC Power Supervision Reports are sent to the central 
station and local printer at the time programmed for 
AC Fail Time
 
AC Tag Along 
Default: 
Yes 
Selection: 
Yes or No 
Yes 
Send AC messages as tag along 
events. 
No 
Do not send AC messages as tag 
along events. 
Send AC Reports only if any other event occurs while 
AC is off-normal.  
If AC Tag Along is set to Yes and a 
subsequent event is generated, the AC 
Fail Event is sent first, before sending 
any subsequent events.