D9412GV3/D7412GV3 | Program Entry Guide | 3.0  Points 
EN | 89 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
 
P ## Type  
Description 
Keyswitch Maintained:
 Program P## Pt Response as 1. Do not connect initiating devices to 
a Keyswitch point. 
   Normal: 
The area is disarmed. 
  Short: 
A short is a trouble when the area is disarmed. A short is an alarm when the 
area is armed. When this point changes from shorted to normal or open, it 
restores. 
  Open: 
When this point changes from normal to open, the area arms.  
Program Point Response as 2, the point responds as follows: 
   Normal: 
When this point changes from open to normal, the area arms. 
  Open: 
The area is disarmed. 
  Short: 
A short is a trouble when the area is disarmed. A short is an alarm when the 
area is armed. When this point changes from shorted to normal or open, it 
restores. 
4* 
Trouble and Restoral Reports are not sent if Local While Disarmed is Yes
Alarm and Restoral Reports are not sent if Local While Armed is Yes
Keyswitch Momentary: Used for area arming and disarming. Point Response must be 
programmed 1. Do not connect initiating devices to a Keyswitch point. 
   N
SN:
 
 
When this point momentarily changes from normal to shorted to normal, it 
toggles the armed state of the area. 
  Open: 
An open is a trouble while the point is disarmed. An open is an alarm while 
the point is armed. 
When this point changes from open to normal, it restores. 
5* 
Trouble and Restoral Reports are not sent if Local Disarmed is Yes
Open/Close Point: Used for point arming and disarming. Point Response must be 
programmed 1. Local bells are silenced through the keypad. 
 
  
Normal: 
The point is armed and sends a Point Closing Report. A Point Closing Report 
is not sent if Local Armed is Yes
  Open: 
An open is an alarm when the point is armed. An open is a trouble when the 
point is disarmed. Alarm and Restoral Reports are not sent if Local 
Disarmed
 is Yes
6* 
  Short: 
The point is disarmed and sends a Point Opening Report. A Point Opening 
Report is not sent if Local Armed is Yes
*  Keyswitch Points: Special rules apply to points used for Keyswitch functions. These special point types do not 
respond the same way to the point response entry as Point Types 1, 2, and 3.  
(Continued on next page.)