White Rodgers 1F80ST-0471 User Manual

Page of 8
5
INSTALLER/CONFIGURATION MENU 
4.  Energy Management Recovery: (this step is skipped if  
confi gured to be non-programmable). 
 
Energy Management Recovery (E) On enables the  
thermostat to start heating or cooling early to make the 
building temperature reach the program setpoint at the 
time you specify. Heating will start 5 minutes early for 
every 1° of temperature required to reach setpoint.
 
Example: If E On is selected and have your heating 
programmed to 65° at night and 70° at 7 AM. If the 
building temperature is 65°, the difference between 
65° and 70° is 5°. Allowing 5 minutes per degree, the 
thermostat setpoint will change to 70° at 6:35 AM. Cooling 
allows more time per degree, because it takes longer to 
reach set temperature.
5, 6 & 7. Cycle Rate Selection – The factory default settings  
with SS/HP switch in SS position for Heat is medium  
cycle (ME) and Cool is fast cycle (AL). For Heat Pump  
(HP), the default setting is fast cycle (AL). 
 
To change cycle rate, press the 
 or 
 key.
 
Cycle rate differentials for different settings are:
 MODE 
Fast 
Medium 
Slow
 
 
AL 
   ME 
bA
 
Heat  (SS) 
0.4°F 
0.6°F 
1.8°F
 
Cool  (SS) 
1.2°F 
– 
1.7°F
 
Heat Pump (HP) 
1.2°F 
– 
1.7°F
8.  Select Compressor Lockout CL OFF or ON – Selecting 
CL ON will cause the thermostat to wait 5 minutes 
between cooling cycles. This is intended to help protect 
the compressor from short cycling. Some newer 
compressors already have a time delay built in and do not 
require this feature. Your compressor manufacturer can tell 
you if the lockout feature is already present in their system. 
When the thermostat compressor time delay occurs, it  
will fl ash the setpoint for up to fi ve minutes.
9.  System Mode Confi guration – This thermostat is 
confi gured for Calor and Frio with Auto changeover  
(SISTEMA switch with Frio Off Calor Auto) default. It can 
also be confi gured for Calor and Frio (Frio Off Calor),  
Calor only with fan (Off Calor), Calor only without fan, 
Auto only (Auto Off), and Frio only (Frio Off).
10. Select Backlight Display – The display backlight 
improves display contrast in low lighting conditions. When 
the "C" terminal is powered, selecting backlight L ON will 
keep the light on continuously. Select backlight OFF will 
keep the light on momentarily after any key is pressed. 
When the "C" terminal is not powered, the light will 
be on momentarily after any key is pressed no matter 
whether the backlight is selected ON or OFF.
11. Select Temperature Display Adjustment 4 LO to 4 HI 
Allows you to adjust the room temperature display up 
to 4° higher or lower. Your thermostat was accurately 
calibrated at the factory, but you have the option to change 
the display temperature to match your previous thermo 
stat. The current or adjusted room temperature will be 
displayed on the left side of the display.
12. Select F° or C° Readout – Changes the display readout 
to Centigrade or Fahrenheit as required.
13. Select Filter Replacement Reminder and Set Run Time 
Select the "Cambiar Filtro" (Change Filter) reminder On 
or OFF. If selected On, press MENU to select the time 
period from 25 to 1975 hours in 25 hours increments. 
In a typical system, 200 hours (default) of run time is 
approximately 30 days. After the selected time of blower 
operation, the thermostat will display "Cambiar Filtro" 
(Change Filter) as a reminder to change or clean your air 
fi lter. When "Cambiar Filtro" (Change Filter) is displayed, 
press MENU button to clear the display and restart the 
time to the next fi lter change.