D9412GV2/D7412GV2 | Operation and Installation Guide | 7.0  Telephone Connections 
 
30 
Bosch Security Systems, Inc. | 5/05 | F01U003641B 
 
7.11.3  Installing the D928 
Mounting 
Mount the D928 on the lower right side of the 
enclosure using the screws provided with the switcher. 
Wiring 
The D928 has two flying leads. The green lead 
monitors AC power. The black lead is the ground 
reference for the AC Power LED. 
1.
 
Connect the green lead from the D928 to  
Terminal 1. 
2.
 
Connect the black lead from the D928 to 
Terminal 9. 
Telephone Connections 
1.
 
Plug one end of the ribbon cable provided into J4 
on the control panel. Plug the other end of the 
ribbon cable into the ACCESSORY connector on 
the control panel. 
2.
 
Plug one end of the D162 phone cord provided 
into the telco jack. Plug the other end of the phone 
cord into the telco jack on the control panel. Refer 
to 
Error! Reference source not found.
 for phone 
cord lengths. 
Table 9: 
Phone Cord Lengths 
 
Phone Cord 
Length 
D161 
2.4 m (8 ft) 
D162 
61 cm (2 ft) 
3.
 
Plug one end of a D161 or D162 phone cord into 
J1 on the control panel. Plug the other end of the 
phone cord into the RJ31X or RJ138X for the 
primary telephone line.  
4.
 
Plug one end of a D161 or D162 phone cord into 
J2 on the control panel. Plug the other end of the 
phone cord into the RJ31X or RJ138X for the 
secondary telephone line. Refer to 
Error! 
Reference source not found.
 for phone cord 
lengths. 
 
 
 
If you installed a D928 before November 19, 
2001 on a D9412GV2 or D7412GV2, 
disconnect AC power from the control panel 
(battery must remain connected) and observe 
the green LED.  
If this LED glows dimly, contact Customer 
Service at (800)289-0096 for a replacement 
module at no charge. 
 
7.11.4  D928 Status LEDs 
Four LEDs mounted on the front edge of the D928 
Module show the status of AC power for the control 
panel, the status of the two telephone lines, and 
communication failure (Figure 11 on page 33). When 
programmed and operating normally, only the green 
AC power status LED is lit. 
AC Power LED 
The green AC Power Status LED lights when AC 
power is applied to Terminals 1 and 2 on the control 
panel. 
Phone Line Fail LEDs 
Two yellow Phone Line Status LEDs (one for the 
primary telephone line, one for the secondary 
telephone line) light if the voltage on the telephone line 
falls to between 5.0 and 7.0 VDC, without the 
corresponding current of 13 mA. The control panel 
monitors the faulty telephone line for the programmed 
interval before indicating a trouble condition. Refer to 
Section 7.8 Telephone Line Monitor on page 28 for a 
description of phone line monitor operation. 
Communication Failure LED 
The yellow Communication Failure LED lights when 
the system is in communication failure. The LED turns 
off when communication restores. Refer to Section 7.10 
Communication Failure
 on page 28.